Toshiba GR-200 Series Instruction Manual page 50

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

required, Block is set for the scheme switch [OC1-ARCBlk]. Block is set for the scheme switch
[OC1-ARCBlk] as a default.
Signal of OC trip
(v)
When a user requires an alarm signal in place of the trip signal; for example, set Alarm for the
scheme switch [OC1-UseFor]. Trip is set for the scheme switch [OC1-UseFor] for the normal
trip operation.
Scheme logic
2.1.7
The scheme logic for both the non-directional and the directional OC1 element is illustrated in
Figure 2.1-8; Figure 2.1-9 shows grouping commands for the trip circuit (TRC). Each phase of
the OC1 element issues a pick-up when a current has been exceeded over the setting, and the
pick-up signal is transferred to into the TRC as a trip signal. (For more information about the
TRC, see Chapter 2.23)
For DT characteristic
A
OC1
B
C
For IDMT characteristic
A
OC1 PU
B
C
From ICD
ICD-A
&
≥1
ICD-B
&
≥1
&
ICD-C
≥1
≥1
&
Block-AllP
OC1-2PBlk
Block-PerP
OC1-EN
On
From VTF
VTF_DETECT
OC1-VTFBlk
8000011BB0
800001EBB0 OC1_BLOCK
8000011BB1
800001EBB4 OC1_INST_OP
†Note: The presence of 'OC1-OR' and 'OC1PU-OR' signals depends on the operation
characteristic defined with setting [OC1_Timer], as shown in Table 2.1-7.
≥1
≥1
8000011C20
&
&
8100011C21
&
&
8200011C22
&
&
8000011C24
&
&
8100011C25
&
&
8200011C26
&
&
OC1-Timer
&
Block
≥1
Figure 2.1-8 Scheme logic for the OC1
TOC1
&
t
0
&
t
0
&
t
0
0.00–300.00s
≥1
&
&
≥1
&
&
≥1
&
&
DT
IEC-NI
IEC-VI
IEC-EI
UK-LTI
IEEE-MI
IEEE-VI
IEEE-EI
US-C02
US-C08
ORIGINAL
- 31 -
6F2T0200 (0.15)
8100011B60
8100011B61
≥1
&
≥1
&
≥1
&
≥1
≥1
&
&
8000011B68
&
≥1
&
&
&
3POR
&
OC1-OPMD
2OUTOF3
Trip
&
OC1-UseFor
Alarm
Block
OC1-ARCBlk
GRE200 (1,2)
OC1-OR†
OC1PU-OR†
To Grouping logic
OC1-OPT-AR
OC1-OPT-BR
OC1-OPT-CR
OC1-OPT
OC1-OPT-TRIP
OC1-OPT-ALARM
OC1-ARC-BLOCK