Toshiba GR-200 Series Instruction Manual page 468

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

4.1-13 for PLC#1, Table 4.1-14 for PLC#2, Table 4.1-17 and Table 4.1-19 for output
signals.
Note: The "Operate failed" signal is issued when the state-change is not detected when
‡‡
the time set by the [DPOS01-RST] has been reached.
Receiving "Operate command Off" from the remote-end
(ii)
Figure 4.1-21 depicts the reception of the operate command 'Off ' from the remote-end.
Wait for a command
Select stage
Select command On from the remote-end
Select command Off from the remote-end
Select command On from the local-end
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Figure 4.1-21 Outline of Operate command 'Off'
Mapping required for Input point
Figure 4.1-22 illustrates the operate logic when an "Operate command Off (Remote-Off-
Control)" signal is applied to the DPOS01 logic. The input-point "DEV01_CONTROL_REQ" is
used for the reception of the "Operate command Off (Remote-Off-Control)".
Output signal to BO
The DPOS01 function, in Figure 4.1-22, can issue an "Operate" signal at the output-point
"DPOS01_FEX_BO", when the DPOS01 function determines that the input signal "Remote-
Off-Control" is true.
Wait for a next command
Operate command On from the remote-end
Operate command Off from the remote-end
Operate logic
Signal reception in
IEC61850
Operate command On l from the local-end
Operate command Off from the local-end
Operate command On by the PLC function
Operate command Off by the PLC function
- 449 -
6F2T0200 (0.15)
Success
Operation
Signal output
decision
Do nothing
Failed
GRE200 (1,2)