Setting of CHK_PLC_DAT (Function PLC_DAT: 223202)
Setting item
CHK_PLC_DAT:Sw
--- / Serious error / Serious error(Comm) /
CHK_PLC_DAT:Lvl
Setting of CHK_PING (Function ID: 223601 and 223602)
Setting item
CHK_PING1:Sw
--- / Serious error / Serious error(Comm) /
CHK_PING1:Lvl
PING_IP_ADRS
CHK_PING2:Sw
--- / Serious error / Serious error(Comm) /
CHK_PING2:Lvl
PING_IP_ADRS
Setting of CHK_CMLV (Function ID: 224001)
Setting item
CHK_CMLV_DAT:Sw
--- / Serious error / Serious error(Comm) /
CHK_CMLV_DAT:Lvl
Setting of CHK_GOOSERCV (Function ID: 223501)
Setting item
CHK_GOOSERCV:Sw
--- / Serious error / Serious error(Comm) /
CHK_GOOSERCV:Lvl
Setting of CHK_DPOS (Function ID: 229101)
Setting item
CHK_DPOS1:Sw
--- / Serious error / Serious error(Comm) /
CHK_DPOS1:ULvl
--- / Serious error / Serious error(Comm) /
CHK_DPOS1:FLvl
CHK_DPOS2:Sw
--- / Serious error / Serious error(Comm) /
CHK_DPOS2:ULvl
--- / Serious error / Serious error(Comm) /
CHK_DPOS2:FLvl
CHK_DPOS3:Sw
--- / Serious error / Serious error(Comm) /
CHK_DPOS3:ULvl
--- / Serious error / Serious error(Comm) /
CHK_DPOS3:FLvl
...
Range
Off / On
Minor error / Alarm / Warning
Range
Off / On
Minor error / Alarm / Warning
*.*.*.*
Off / On
Minor error / Alarm / Warning
*.*.*.*
Range
Off / On
Minor error / Alarm/ Warning
Range
Off / On
Minor error / Alarm / Warning
Range
Off / On
Minor error / Alarm / Warning
Minor error / Alarm / Warning
Off / On
Minor error / Alarm / Warning
Minor error / Alarm / Warning
Off / On
Minor error / Alarm / Warning
Minor error / Alarm / Warning
....
- 729 -
Contents
Enable switch
Error level
Contents
Enable switch
Error level
Ping target IP address
Enable switch
Error level
Ping target IP address
Contents
Enable switch
Error level
Contents
Enable switch
Error level
Contents
Enable switch to supervising
the DPOS01
Error level for undefined error
at DPOS01
Error level for faulty error at
DPOS01
Enable switch to supervising
the DPOS02
Error level for undefined error
at DPOS02
Error level for faulty error at
DPOS02
Enable switch to supervising
the DPOS03
Error level for undefined error
at DPOS03
Error level for faulty error at
DPOS03
...
6F2T0200 (0.15)
Default setting value
Notes
On
Minor error
Default setting value
Notes
Off
Minor error
192.168.1.1
Off
Minor error
192.168.1.1
Default setting value
Notes
On
Minor error
Default setting value
Notes
On
Minor error
Default setting value
Notes
On
Alarm
Minor error
On
Alarm
Minor error
On
Alarm
Minor error
....
GRE200 (1,2)