11.3.10 Setting
Setting of 61850(Function ID: 301001)
Setting item
GOINT
850BLK
850AUT
850KEEPALIVE
TCMD
Unit
Range
s
1 to 120
sec.
Maximum GOOSE resend interval
Off/On
IEC 61850 enable/disable
Off/On
Authentication of IEC 61850 association
1 to 120
sec.
TCP 'KeepAlive' time for IEC 61850
Off/On
Set 'T' in 'CommTerm' as actual Time
- 785 -
Default setting
Contents
6F2T0200 (0.15)
Notes
value
2
Off
Off
20
Off
GRE200 (1,2)