Mapping output data
(ii)
The user should group the DPOS01 signals with regard to GOOSE and REPORT; the user
should map them for IEC 61850 communication using GR-TIEMS. (Figure 4.1-55 illustrates
how to map a signal); it indicates that the signals for the DPOS01 function are required to map
for IEC 61850 communications.
Table 4.1-34 Mapping signals required for CSWI4 object in DPOS01 function
Object_reference
Ctrl/CSWI4$Pos$origin
orCat
Ctrl/CSWI4$Pos$origin
orIdent
Ctrl/CSWI4$Pos
stVal
Ctrl/CSWI4$Pos
q
Ctrl/CSWI4$Pos
t
Ctrl/CSWI4$Pos
stSeld
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.1-55 Attribute mapped into DPCSO object of CSWI4
Mapping input data
(iii)
The DPOS01 function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point " DEV01_CONTROL_REQ" to the IEC61850 communication. Table
4.1-35 shows the input "DEV01_CONTROL_REQ" and the Object reference "Ctrl/CSWI4$Pos" ;
the user should map the input-point to the Object reference having attribute CO†. Figure 4.1-56
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; "CO" stands for "Control" in
the functional constraint (FC).
Attribute
Type
orCategory
Octet64
Dbpos
Quality
Timestamp
BOOLEAN
- 483 -
FC
Signal Number
ST
512001 3103011008
ST
512001 6A03011009
ST
512001 3103011001
ST
512001 3103011005
ST
512001 9003011006
ST
512001 0003011D90
Drag and drop
6F2T0200 (0.15)
Signal Name
DPOS01_3PH_ORCAT
DPOS01_3PH_ORIDENT
DPOS01_3PH_STATE
DPOS01_3PH_QUALITY
DPOS01_3PH_TIMESTAMP
DPOS01_STD_RPT
GRE200 (1,2)