Toshiba GR-200 Series Instruction Manual page 202

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting
2.16.6
Setting of OVS_MV (Function ID: 461181)
Setting device
OVS1-EN
OVS2-EN
OVS3-EN
OVS4-EN
OVS1
OVS1-Timer
DT
OVS1
TOVS1
OVS1-DPR
IDMT
OVS1
OVS1-DPR
OVS1-TMS
TOVS1R
ORG
OVS1
OVS1-DPR
OVS1-TMS
TOVS1R
Output
OVS1-VTFBlk
OVS1-UseFor
OVS2
OVS2-Timer
DT
OVS2
TOVS2
OVS2-DPR
IDMT
OVS2
OVS2-DPR
OVS2-TMS
TOVS2R
ORG
OVS2
OVS2-DPR
OVS2-TMS
TOVS2R
Output
OVS2-VTFBlk
OVS2-UseFor
OVS3
OVS3-Timer
DT
OVS3
TOVS3
OVS3-DPR
IDMT
OVS3
OVS3-DPR
OVS3-TMS
TOVS3R
ORG
OVS3
OVS3-DPR
OVS3-TMS
TOVS3R
Output
OVS3-VTFBlk
OVS3-UseFor
OVS4
OVS4-Timer
DT
OVS4
TOVS4
OVS4-DPR
IDMT
OVS4
Range
Unit
Off / On
- OVS1 protection scheme switch
Off / On
- OVS2 protection scheme switch
Off / On
- OVS3 protection scheme switch
Off / On
- OVS4 protection scheme switch
DT / IDMT / Original
- OVS1 delay type
1.0 - 220.0
V OVS1 threshold
0.00 - 300.00
s OVS1 operating delay time (in DT mode)
10 - 100
% OVS1 drop-out/pick-up ratio
1.0 - 220.0
V OVS1 threshold
10 - 100
% OVS1 drop-out/pick-up ratio
0.010 - 100.000
- OVS1 time multiplier (in IDMT mode)
0.0 - 300.0
s OVS1 definite time reset delay
1.0 - 220.0
V OVS1 threshold
10 - 100
% OVS1 drop-out/pick-up ratio
0.010 - 100.000
- OVS1 time multiplier (in ORG mode)
0.0 - 300.0
s OVS1 definite time reset delay
Non / Block
- OVS1 operation block by VTF
Trip / Alarm
- OVS1 used for trip or alarm
DT / IDMT / Original
- OVS2 delay type
1.0 - 220.0
V OVS2 threshold
0.00 - 300.00
s OVS2 operating delay time (in DT mode)
10 - 100
% OVS2 drop-out/pick-up ratio
1.0 - 220.0
V OVS2 threshold
10 - 100
% OVS2 drop-out/pick-up ratio
0.010 - 100.000
- OVS2 time multiplier (in IDMT mode)
0.0 - 300.0
s OVS2 definite time reset delay
1.0 - 220.0
V OVS2 threshold
10 - 100
% OVS2 drop-out/pick-up ratio
0.010 - 100.000
- OVS2 time multiplier (in ORG mode)
0.0 - 300.0
s OVS2 definite time reset delay
Non / Block
- OVS2 operation block by VTF
Trip / Alarm
- OVS2 used for trip or alarm
DT / IDMT / Original
- OVS3 delay type
1.0 - 220.0
V OVS3 threshold
0.00 - 300.00
s OVS3 operating delay time (in DT mode)
10 - 100
% OVS3 drop-out/pick-up ratio
1.0 - 220.0
V OVS3 threshold
10 - 100
% OVS3 drop-out/pick-up ratio
0.010 - 100.000
- OVS3 time multiplier (in IDMT mode)
0.0 - 300.0
s OVS3 definite time reset delay
1.0 - 220.0
V OVS3 threshold
10 - 100
% OVS3 drop-out/pick-up ratio
0.010 - 100.000
- OVS3 time multiplier (in ORG mode)
0.0 - 300.0
s OVS3 definite time reset delay
Non / Block
- OVS3 operation block by VTF
Trip / Alarm
- OVS3 used for trip or alarm
DT / IDMT / Original
- OVS4 delay type
1.0 - 220.0
V OVS4 threshold
0.00 - 300.00
s OVS4 operating delay time (in DT mode)
10 - 100
% OVS4 drop-out/pick-up ratio
1.0 - 220.0
V OVS4 threshold
- 183 -
Contents
6F2T0200 (0.15)
Default
Note
Off
Off
Off
Off
DT
120.0
1.00
100
120.0
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
DT
120.0
1.00
100
120.0
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
DT
120.0
1.00
100
120.0
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
DT
120.0
1.00
100
120.0
GRE200 (1,2)