Toshiba GR-200 Series Instruction Manual page 457

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Double Command Blocking detected*1
Other devices traveling detected*2
From TRC*3
General trip
GEN. TRIP
Additional condition (PLC#1 connection point)
512001 810301EE62
DPOS01IN_TMP_32
User configurable condition (PLC#2 connection point)
512001 800301EE61
DPOS01IN_TMP_31
From Control hierarchy *8 (PLC#3 connection point)
512001 820301ED50
DPOS01IN_TMP_28
From CMNCTRL
Serious error detection
SERI_ERR
Figure 4.1-13 Select condition logic for 'ON/OFF' in DPOS01
Note: "Double Command Blocking" (DCB) is an operation philosophy in the common
1
control function (CMNCTRL). It can be used to protect the substation. The user
can program it using GR-TIEMS. The DCB operating signal is denoted as "DCB
RCV OR" in Table 4.1-5. For more information, see Chapter
monitoring application
Note: If the event "device-travelling" is detected in the CMNCTRL function, it indicates
2
that another operator is changing the status of a device. Thus, the IED should
inhibit the operation of any device for the duration that the event is detected. The
detected signal is denoted as "Travelling OR" in Table 4.1-5.
Note: If the issue of a trip command is executed by the IED, any control operation is
3
blocked until the trip operation is completed. When the IED has trip circuit
function, the trip command is issued at PLC monitoring point "GEN.TRIP" (see
Table 4.1-5, and p. 266).
Note: Criteria "unmatched conditions" are decided when "Test-bit status" in a command
4
is not identical to "IED test status".
Note: The function "Event suppression" can detect chattering on BI circuits. (See
5
Chapter 4.1.6(i)-3)
Note: A supervision of the Binary IO module can detect connection errors for BI circuits
6
Note: The Common control (CMNCTRL) function can test and check the 'On and Off
7
DPOS01 function (Function ID: 512001)
DCB RCV OR
Unmatched condition detected *4
Traveling OR
Event suppression detected *5
= DPOS01_F_QLT_SPP
BI board connection error detected*6
= DPOS01_F_BI_ERR
Command "ON control" received
Command "OFF control" received
DPOS01_3PH_STATE
(512001 3103011001)
[SCDEN]*7
OFF
[DPOS01-LGSLFFCT]
Fixedlogic
[DPOS01-CTREN]
On
:
1≥
(512001 8103011F5F)
(512001 8203011F60)
&
&
received
Appearance of the
controls in the same
direction
Common controls
(→p. 414)
- 438 -
6F2T0200 (0.15)
1≥
&
&
&
&
*9
Control and
.
GRE200 (1,2)
To select logic
Select condition
.

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2