Toshiba GR-200 Series Instruction Manual page 803

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Table 11.3-7 GOOSE statutes and signal outputs
Signal values
0x0000
0xC000
0xC010
0xC040
0xC080
When wishing to see bare GOOSE outputs†, the user can do in the PLC function; and then,
the user himself has to create GOOSE logics by the PLC editor. Table 11.3-8 shows the bare
GOOSE ones, which the user can find in the PLC function. For example, in order to see the
bare GRE200_Bay1_4 one, pick the SUB_QUAL#3 output.
Data ID
301101 3100001001
301101 3100011001
301101 3100021001
301101 3100031001
301101 3100041001
~~~
301101 31013E1001
301101 31013F1001
†Note: They are described in
them on the GR-TIMES engineering.
Feature of IEC61850 Edition1 option
11.3.9
The IED can have Private logical nodes, which are provided in Editon1_option, which are
designed in Toshiba private specification exclusively. The user can select and add the following
Data object:
LD Class
DO
GGIO
AnInDatUpd
Note: The option1 is designed to transfer the metering values during the fault on the
IEC61850 Edition1.
LCD screen messages
OK
NG
NG
NG
NG
Table 11.3-8 GOOSE output signals
Signal names
SUB_QUAL#0
SUB_QUAL#1
SUB_QUAL#2
SUB_QUAL#3
SUB_QUAL#4
~~~
SUB_QUAL#318
SUB_QUAL#319
Chapter PLC function
Table 11.3-9 LD class in Editon1 option
Content
DataUpdate Trigger is provided for general Data
Object. The structure is the same as AnIn.
- 784 -
GR-TIEMS screen messages
GOOD
QUESTIONABLE
QUESTIONABLE | TEST
QUESTIONABLE | INACCURATE
QUESTIONABLE | INCONSISTENT
Descriptions
GOOSE subscription quality status
GOOSE subscription quality status
GOOSE subscription quality status
GOOSE subscription quality status
GOOSE subscription quality status
~~~
GOOSE subscription quality status
GOOSE subscription quality status
(→ page 598). The user cannot view
6F2T0200 (0.15)
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2