Toshiba GR-200 Series Instruction Manual page 559

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Table 5.6-4 Setting items for binary input circuits of IO#1
Setting of BIO_SLOT_MV (Function ID: 200B41)
Setting items
Common
CMP_NUM
Common for both
BITH1
BI1 and BI2
BI1
BI1_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI2
BI2_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
Common for
BITH2
BI3–BI15
BI3
BI3_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
BI4
BI4_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
...
....
BI15
BI15_CPL
On Delay Timer
Off Delay Timer
INVERSE-SW
Range
Unit
4 - 9
- Counting number to ignore input signals
Level_11 /
Level_12 /
- Threshold level at both BI1 and BI2 of MV-BI1
Level_13 /
Level_14
Off / On
- Switch for programming logic on binary input1
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input2
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Level_21 /
Level_22 /
- Threshold level at BI3–BI15 of MV-BI1
Level_23
Off / On
- Switch for programming logic on binary input3
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
Off / On
- Switch for programming logic on binary input4
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
....
Off / On
- Switch for programming logic on binary input15
0.000 - 300.000
s Setting value for On-delay timer
0.000 - 300.000
s Setting value for Off-delay timer
Normal / Inverse
- Switch to inverse a binary input
- 540 -
Contents
....
6F2T0200 (0.15)
Default
Note
4
Level_12
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
Level_21
Off
0.000
0.000
Normal
Off
0.000
0.000
Normal
....
Off
0.000
0.000
Normal
GRE200 (1,2)