Download Print this page

Toshiba GR-200 Series Instruction Manual page 800

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Quality signal of IEC 61850 communication
11.3.7
Quality information and its attributes are defined in the IEC 61850. Table 11.3-6 shows that
the relations between the definitions in the standard and signals prepared in the IED. The
quality attributes are influenced by the errors and alarms occurred in the IED, and the degree
of those errors are standardized by settings 'Error level' (see Chapter
The quality information is also affected by the test mode executed in the IED (see Chapter
Commissioning and maintenance
Table 11.3-6 Quality signal defined in IEC 61850-7-3
Quality components definition in IEC 61850-7-3
Attribute Name
Validity
good / invalid / reserved / questionable
detailQual
overflow
2
outOfRange
2
badReference
oscillatory
2
Failure
oldData
2
inconsistent
2
Inaccurate
source
2
Test
operatorBlocked
2
Note: M/N/O means rules of attributions. If it is Mandatory (M), it shall be used in the
1
IED. Optionally (O), or conditional mandatory(C) are used depending on the
environment states.
Note: The IEDs of GR-200 series do not carry those attributes—overflow, out Of Range,
2
oscillatory, old Data, inconsistent, source, and operator Blocked.
Note: Detail quality attributes (e.g., overflow, outOfRange, etc. marked with "N") are not
3
included in the Qual_Validity.
).
Attribute value
packed value
(
)
process / substituted
True / False
True / False
- 781 -
6F2T0200 (0.15)
Automatic supervision
IED signal
M/
Default
O/
value
C
1
M
Undecided
(shall be
determined
depending
M
on an error
condition)
M
process
M
False
M
False
GRE200 (1,2)
).
3
Y
N
N
N
N
N
N
N
N
N
Y
N