Goose monitoring status in 61850 communication
11.3.8
IEDs are able to monitor the communication using GOOSE packets, which other IEDs have
sent their information via the network. If the IED can receive the GOOSE packets, the IED
can display them on the information list. Figure 11.3-30 illustrates an example of the GOOSE
monitoring list; it shows all IEDs have reported good status (OK) message, except one IED.
Screen scroll down
Figure 11.3-30 Screen example of GOOSE Monitoring
Note: The IED shall be managed with own subscription information to receive the
GOOSE packets regarding the other IEDs. Thus, the user should edit the
subscription contents (see Figure 11.3-21). The LCD displays the statuses based
on that the user has edited the list of the subscription contents.
Note: Jump to
GOOSE mentoring screen. The user can also find the GOOSE information on the
test screen on GR-TIEMS.
On the LCD screen, the user can find either OK or NG message regarding other IEDs. The
OK/NG message is generated with the information of the GOOSE packet received. Table 11.3-7
illustrates the messages displayed on LCD screen and GR-TIEMS screen.
GOOSE Monitoring
11:12
GRE200_Bay1_1
GRE200_Bay1_2
GRE200_Bay1_3
GRE200_Bay1_4
GRE200_Bay2_1
GRE200_Bay2_2
GRE200_Bay2_3
GRE200_Bay2_4
GRE200_Bay3_1
GRE200_Bay3_2
GRE200_Bay3_3
GRE200_Bay3_4
GRE200_Bay99
GRE200_Bay99
GRE200_Bay99
GRE200_Bay99
Monitoring sub-menu
(see Chapter
- 783 -
Signal names
1/320
SUB_QUAL#0
OK
SUB_QUAL#1
OK
SUB_QUAL#2
OK
SUB_QUAL#3
NG
SUB_QUAL#4
OK
SUB_QUAL#5
OK
SUB_QUAL#6
OK
SUB_QUAL#7
OK
SUB_QUAL#8
OK
SUB_QUAL#9
OK
SUB_QUAL#10
OK
SUB_QUAL#11
OK
SUB_QUAL#316
OK
SUB_QUAL#317
OK
SUB_QUAL#318
OK
SUB_QUAL#319
OK
User interface→ p.
6F2T0200 (0.15)
865) to display the
GRE200 (1,2)