Toshiba GR-200 Series Instruction Manual page 793

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

For example, to let a device execute "Select", "Operate" and "Cancel" commands
from the sever through "CSWI4" and transmit the information to an IED, the user
should map an input point (Data ID) to several variables of "CSWI4" (See Figure
11.3-22). Mapping period for Control shall be 100.
*Note: For more information of the input points, see chapter
Control and monitoring application
SBOW
Oper
Cancel
Figure 11.3-22 Control function mapping
To complete the setting for control function, after mapping data, the user needs
to set BI, BO† in the GR-TIEMS ->Setting.
†Note: For more information for the BI, BO, see Chapter
module
(→p. 533).
(→p. 424).
Mapping
DE V01_ CONTROL_ RE Q
- 774 -
6F2T0200 (0.15)
General control function or
Input DataID
Technical description: Binary IO