Function keys
5.7.4
Function keys (F1 to F5) are provided to jump to other menus during the operation on LCD
screen; the jump destinations are already set as factory default (see Table 5.7-4). However, the
user can program the F1 to F5 keys to jump to user-preferred menus using settings.
Incidentally, the user can program the function key so that a binary signal is generated when
the user presses the function key. For the test, the user can configure to generate a binary test
signal when a key is pressed.
Table 5.7-4 Function keys and jump destinations (default)
Screen jump pressing the function key
(i)
The user can program the F1 to F5 keys as the user-preferred jump keys. For example, when
the user wishes to use the F1 key to jump to another screen, set Screen jump for setting
[Function] in the F1 key (see Table 5.7-6). We shall see the setting in Chapter
Setting sub-menu: Configuration of Function keys
Binary signal generated pressing the function key
(ii)
When the user wishes to generate a binary signal upon occurrence of pressing the F1 key, set
Assign Signal for scheme switch [Function] in the F1 key. If required, for instance, by pressing
F1, a signal can be transfer to BO1 circuit at IO#1-2 slot‡, set Data ID "FUNC-KEY1(240001
310001730)" for setting [Input signal 1] at the BO1‡ circuit. Note that the user should set On
for the scheme switch [BO1_CPL] after the both are connected with setting [Input signal 1].
Figure 5.7-4 shows that a generate signal is transferred and outputted by pressing the F1 key.
Table 5.7-7 shows the other FUNC-KEY2–5. We will see the setting procedure in Chapter
interface: Setting sub-menu: Signal control function
Function
Jump destination as default
Key#
Metering menu
F1
F2
Fault Record menu
F3
Event Record1 menu
F4
Event Record2 menu
F5
Event Record3 menu
- 561 -
.
(→p.882)
.
(→p. 882)
6F2T0200 (0.15)
User interface:
User
GRE200 (1,2)