Setting
2.3.4
CARRIER_COMMON (Function ID: 438001)
Setting items
Carrier_COM
CAR-CHNUM
TCARECCB
TWICOORD
CARRIER_DEF (Function ID: 437001)
Setting items
Carrier_DEF
DEF-CAR
DEF-ECHO
DEF-WKIT
DEFCAR-CHSEL
TDEFCF
TDEFCB
TDEFC
TREBK-DEF
TCHD-DEF
TSBCT-DEF
Output
DEFCAR-ARCBlk
Range
Unit
2-TERM / 3-TERM
- Carrier scheme terminal number
0.00 - 200.00
s Echo enable timer from CB opened
0.000 - 0.100
s Time coordination for UV relay operation
Range
Unit
Off/POP/UOP/BOP
DISCAR scheme enable
Off / On
- Echo function enable
Off / On
- Weak infeed trip function enable
Single / And / Guard
- Carrier channel configuration
0.00 - 0.30
s DEF carrier trip delay time
0.00 - 0.30
s DEF carrier trip delay time
0.00 - 0.30
s DEF carrier trip delay time
0.00 - 10.00
s Current reverse blocking time
0.000 - 0.100
s Coordination timer in BOP function
0.00 - 1.00
s SBCNT timer
Non / Block
- Autoreclose block by DEF carrier trip
- 65 -
Contents
Contents
6F2T0200 (0.15)
Default
Note
2-TERM
0.10
0.000
Default
Note
Off
Off
Off
Single
0.15
0.15
0.00
0.10
0.012
0.10
Block
GRE200 (1,2)