Toshiba GR-200 Series Instruction Manual page 759

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Protocol selection
LAN modules are provided for the IEC61850 and other communication†, and an optional serial
module‡ will be provided for the Modbus RTU or IEC60870-5-103 slave communication.
Figure 11.1-1 illustrates the IED has IEC61850, IEC103 and Modbus, and the user can select
one of them using SLAVE PROTOCOL setting of Setting sub-menu. IEC61850 and others have
its own settings. For example, the IED has settings, such as GOOSE and authentication, for
the IEC61850.
Communication
10:48
1/7
LAN
>
USBCOM
>
RS485
>
SLAVE PROTOCOL
>
IEC61850
>
IEC103 SLV
>
MODBUS
>
Figure 11.1-1 Protocol selected by SLAVE PROTOCOL setting
†Note: The number of the communication protocol embedded in an IED is depending on
the software selection of that IED, which the user can identify using an ordering
code at positon U on page 1004. See
supported here (even though the DNP3.0 is displayed on the LCD).
‡Note: We have discussed that optional communication interface on page 528. See
Technical description: Signal processing and communication module
CNM_SLAVE (Function ID: 300001)
Setting item
Slave Protocol
IEC61850 / IEC103 / Modbus
Element ID
Name
3100013406
ProcType
SLAVE PROTOCOL
10:48
Slave Protocol
IEC61850
Appendix: Ordering
Range
Protocol selection
Description
A type of the protocol selected in the IED
- 740 -
SLAVE PROTOCOL
1/1
10:48
+
IEC61850
IEC103
DNP3.0†
Modbus
. The DNP3.0 is not
Contents
6F2T0200 (0.15)
1/4
.
Default setting value
IEC61850
GRE200 (1,2)