Toshiba GR-200 Series Instruction Manual page 889

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Figure 12.4-14 Power Value display
Table 12.4-1 Operation means for data reset or data revise
Step
Display
Operation key
1
[>]
2
[+]
Note: In order to secure the reliability, the reset and revision items are controlled by the
1
vendor.
Note: The number of digits for the power value can be reduced based on the units kW,
2
MW and kvar+. For instance when the power is measured as "123,456kW" then it
is displayed as "123MW". If this value has to be changed then the user can key in a
new compensated value. For example, if "78MW" should be displayed on the IED
screen even though the measured value is "123,456kW" then the user should key in
the new value of "78MW". Note that the compensated value "78MW" is "78,000kW",
and it is not "78,456kW" or "123,456kW". Note that the compensated value will be
affected when there is a change in CT ratio setting. That is, when the user key in a
value of "78MW" for the CT ratio of "2000:1" and later when the CT ratio is changed
from "2000:1" to "4000:1", then the value is displayed as "156MW" on the IED screen.
Therefore when the CT ratio setting is changed, the user should key in the value of
"78MW" again to display the compensated value.
Counter sub-menu: the name and number of statistical items are shown in
two lines. When an item is revised, a [+] mark is shown at the end of the first
line.
Figure 12.4-15 Counter sub-menu display
To change the counter number, follow the steps as shown in Figure 12.4-16.
Power Value
10:48
Wh+
0.0MWh
Wh-
0.0MWh
varh+
0.0Mvarh
Remark
Press ► key to go to the sub-menu
Press ENTER key to execute reset or revise. After
ENTER
executing, a confirmation dialog screen displays.
Counter
10:48
COUNT1 (No Assign)
+
0
COUNT2 (No Assign)
+
0
COUNT3 (No Assign)
+
- 870 -