[Off Delay Timer], respectively.
Logic level inversion
When the inversion is required, set Inverse for the setting [INVERSE-SW]. Normal is for non-
inversion.
Logic timer switch
In order that the BO can have a programmable reset characteristic, switch and setting are
provided. The characteristic are of four types and the user can select a type: (1) Instant (Off),
(2) Delay, (3) Dwell, and (4) Latch type:
Instant type: when the user wishes to output a BO signal without the characteristics, set Off
for the scheme switch [TIMER-SW].
Delay type: if the user requires a BO signal with a delayed characteristic, set Delay for scheme
switch [TIMER-SW]; then set delay width using setting [Logic timer].
Dwell type: if required a BO output made of one shot pulse, set Dwell for the switch [TIMER-
SW]; then, set the value of the pulse width using setting [Logic timer]. If the
arrival signal is shorter than the setting [Logic timer], the pulse width will be
equal to the setting value. Conversely, if the arrival signal is longer than that of
the set value, the pulse width will be equal to the width of the arrival signal.
Latch type: If required a BO output to be removed by a reset signal, enter that Data ID for
setting [Reset signal] and set Latch for the switch [TIMER-SW]. The Data ID may
come from other functions.
Note: When Latch is set, the BO circuit state will be sustained during power turn-on/off.
CPL switch
The user should set On for scheme switch [BO*_CPL] for respective circuits, when the BO
circuits should work depending on the settings. Conversely, set Off if the BO circuit should run
with the signal enters at PLC connection point 'BO*_SOURCE'.