Download Print this page

Toshiba GR-200 Series Instruction Manual page 589

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Synchronization using BI signal
(iii)
When accurate1Hz square-wave can be supplied as a reference clock, the clock function can
make the time synchronization. The 1Hz square-wave is transferred using a binary input
circuit (BI).
Example of time synchronization with a BI circuit
Figure 5.8-7 exemplifies that the 1Hz square-wave is inputted at the BI1†.
Signal generator
1Hz squire wave
Figure 5.8-7 IED connected with the signal generator through a MV-BI module
†Note: It is just used for the explanation; hence, another BI circuit should be selected in
accordance with wiring cables. For more information of the BI circuit, see Chapter
5.6.
Setting procedure
The user should make the following steps in respective IEDs.
1)
Set BI for the setting [Time Sync Src]; then set On for the setting [BI-SYNC].
2)
Check BI is shown under the ActivSyncSrc, as shown in Figure 5.8-8.
3)
Set a Data_ID for setting [BI_ID]. For example, as shown in the Figure 5.8-7, when
the user wishes to inject the signal at the BI1 on the IO#1 slot, the user should set
IED
MV-BI*
(200B41 8001001111)
(+)
1
BI1
2
(-)
(+)
3
BI2
4
(-)
(+)
5
BI3
(+)
6
BI4
(+)
7
BI5
(+)
8
BI6
(+)
9
BI7
(-) 18
19
Fail
20
IO#1-1
- 570 -
6F2T0200 (0.15)
BI1
Setting [BI_ID]
Clock
GRE200 (1,2)

Advertisement