Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Input
Command "Remote-On-Control"
512001_7003016D08
DEV01_CONTROL_REQ
ILK† condition ("ON") passed
DPOS01-Close
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
Figure 4.1-2 Select 'On' from the remote-end in DPOS01
†Note: The software interlocking (ILK) function provides the operation criteria for "On".
The ILK function is discussed separately; note that the operation criteria is
defined by the ILK function itself (i.e., the user cannot set the condition).
‡Note: A "select condition" signal is provided from the select condition scheme. For more
information, see Figure 4.1-13.
*Note: The DPOS01 function can run in either the "SBO mode" or the "DIR mode" using
a signal called "ctlmodel" when communication is implemented using IEC61850.
To use this signal, the user must map it for IEC61850 communication.
Note: To identify the input and output points of the other DPOS logics, see Table 4.1-4
††
and Table 4.1-8.
Select logic in DPOS01
DPOS01 function (Function ID: 512001)
For SBO operation
Select command
with ILK† condition
For DIR operation
Operate command
with ILK† condition
For SBO operation
Select command
without ILK† condition
For DIR operation
Operate command
without ILK† condition
In SBO operate
In DIR operate
Select condition‡
- 426 -
&
1≥
&
&
0
&
0
&
††
6F2T0200 (0.15)
Output
To "Wait for a next
command"
To BO connection
DPOS01_OSL_BO_CSF"
(512001_8603011DC6)
t
Select on "Success"
0.1s
To "Wait for a command"
t
Select "Failed"
0.6s
GRE200 (1,2)