OC_MV (Function ID: 440081)
Setting items
OC2-kr
OC2-b
Output
OC2-2fBlk
OC2-VTFBlk
OC2-OPMD
OC2-UseFor
OC2-ARCBlk
OC2-Act-Stop
OC2-Act-Start
OC2-Act-Run
OC3
OC3-Dir
OC3-Angle
OC3-Timer
DT
OC3
OC3-DPR
TOC3
IEC
OC3
OC3-DPR
OC3-TMS-IEC
TOC3R
UK
OC3
OC3-DPR
OC3-TMS-UK
TOC3R
IEEE
OC3
OC3-DPR
OC3-TMS-
IEEE
OC3-Rtimer
TOC3R
OC3-RTMS-
IEEE
US
OC3
OC3-DPR
OC3-TMS-US
OC3-Rtimer
TOC3R
OC3-RTMS-US
ORG
OC3
OC3-DPR
OC3-TMS-ORG
OC3-Rtimer
TOC3R
Range
Unit
0.00000 - 500.00000
- OC2 user original curve coefficient
0.00000 - 10.00000
- OC2 user original curve coefficient
Non / Block-AllP /
- OC2 operation block by 2f-detection
Block-PerP
Non / Block
- OC2 operation block by VTF
3POR / 2OUTOF3
- OC2 operation mode
Trip / Alarm
- OC2 used for trip or alarm
Non / Block
- Autoreclose block by OC2
Enabling OC2 calculation the motor when
Off / On
-
motor status is in stop status
Enabling OC2 calculation the motor when
Off / On
-
motor status is in start-up status
Enabling OC2 calculation the motor when
Off / On
-
motor status is in running status
NonDir / Forward /
- OC3 directional characteristic
Reverse
-90 – 90
deg OC3 directional characteristic angle
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OC3 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A OC3 threshold (in DT mode)
10 - 100
% OC3 drop-out/pick-up ratio
0.00 - 300.00
s OC3 operating delay time (in DT mode)
0.02 - 25.00
A OC3 threshold (in IDMT mode)
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of IEC inverse curve
0.00 - 300.00
s OC3 definite time reset delay
0.02 - 25.00
A OC3 threshold (in IDMT mode)
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of UK inverse curve
0.00 - 300.00
s OC3 definite time reset delay
0.02 - 25.00
A OC3 threshold (in IDMT mode)
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of IEEE inverse curve
DEF / DEP
- OC3 reset delay type of IEEE
0.00 - 300.00
s OC3 definite time reset delay
OC3 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC3 threshold (in IDMT mode)
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of US inverse curve
DEF / DEP
- OC3 reset delay type of US
0.00 - 300.00
s OC3 definite time reset delay
OC3 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC3 threshold (in IDMT mode)
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of ORG inverse curve
DEF / DEP
- OC3 reset delay type of US
0.00 - 300.00
s OC3 definite time reset delay
- 35 -
Contents
6F2T0200 (0.15)
Default
Note
0.00000
0.00000
Non
Non
3POR
Trip
Block
Off
Off
Off
NonDir
-45
DT
1.00
100
1.00
1.00
100
1.000
0.00
1.00
100
1.000
0.00
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
GRE200 (1,2)