OCN_MV (Function ID:443081)
Setting items
OCN3-a
OCN3-c
OCN3-kr
OCN3-b
Output
OCN3-2fBlk
OCN3-VTFBlk
OCN3-CTFBlk
OCN3-UseFor
OCN3-ARCBlk
OCN4
OCN4-Dir
Fwd/
OCN4-Angle
Rev
OCN4-Vpol
OCN4-Timer
DT
OCN4
OCN4-DPR
TOCN4
IEC
OCN4
OCN4-DPR
OCN4-TMS-
IEC
TOCN4R
UK
OCN4
OCN4-DPR
OCN4-TMS-
UK
TOCN4R
IEEE
OCN4
OCN4-DPR
OCN4-TMS-
IEEE
OCN4-Rtimer
TOCN4R
OCN4-RTMS-
IEEE
US
OCN4
OCN4-DPR
OCN4-TMS-US
OCN4-Rtimer
TOCN4R
OCN4-RTMS-
US
ORG
OCN4
OCN4-DPR
OCN4-TMS-
ORG
OCN4-Rtimer
TOCN4R
OCN4-RTMS-
ORG
Range
Unit
0.00000 - 10.00000
- OCN3 user original curve coefficient
0.00000 - 10.00000
- OCN3 user original curve coefficient
0.00000 - 500.00000
- OCN3 user original curve coefficient
0.00000 - 10.00000
- OCN3 user original curve coefficient
Non / Block
- OCN3 operation block by 2f-detection
Non / Block
- OCN3 operation block by VTF
Non / Block
- OCN3 operation block by CTF
Trip / Alarm
- OCN3 used for trip or alarm
Non / Block
- Autoreclose block by OCN3
NonDir / Forward /
- OCN4 directional characteristic
Reverse
-90 - 90
deg OCN4 directional characteristic angle
0.5 - 25.0
V OCN4 polarizing voltage level
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OCN4 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A OCN4 threshold (in DT mode)
10 - 100
% OCN4 drop-out/pick-up ratio
0.00 - 300.00
s OCN4 operating delay time
0.02 - 25.00
A OCN4 threshold (in IDMT mode)
10 - 100
% OCN4 drop-out/pick-up ratio
0.010 - 50.000
- OCN4 time multiplier of IEC inverse curve
0.00 - 300.00
s OCN4 definite time reset delay
0.02 - 25.00
A OCN4 threshold (in IDMT mode)
10 - 100
% OCN4 drop-out/pick-up ratio
0.010 - 50.000
- OCN4 time multiplier of UK inverse curve
0.00 - 300.00
s OCN4 definite time reset delay
0.02 - 25.00
A OCN4 threshold (in IDMT mode)
10 - 100
% OCN4 drop-out/pick-up ratio
0.010 - 50.000
- OCN4 time multiplier of IEEE inverse curve
DEF / DEP
- OCN4 reset delay type of IEEE
0.00 - 300.00
s OCN4 definite time reset delay
OCN4 dependent reset time multiplier of
0.010 - 50.000
-
IEEE inverse curve
0.02 - 25.00
A OCN4 threshold (in IDMT mode)
10 - 100
% OCN4 drop-out/pick-up ratio
0.010 - 50.000
- OCN4 time multiplier of US inverse curve
DEF / DEP
- OCN4 reset delay type of US
0.00 - 300.00
s OCN4 definite time reset delay
OCN4 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OCN4 threshold (in IDMT mode)
10 - 100
% OCN4 drop-out/pick-up ratio
0.010 - 50.000
- OCN4 time multiplier of US inverse curve
DEF / DEP
- OCN4 reset delay type of ORG
0.00 - 300.00
s OCN4 definite time reset delay
OCN4 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
- 105 -
Contents
6F2T0200 (0.15)
Default
Note
0.00000
0.00000
0.00000
0.00000
Non
Non
Non
Trip
Block
NonDir
-45
3.0
DT
0.40
100
1.00
0.40
100
1.000
0.00
0.40
100
1.000
0.00
0.40
100
1.000
DEF
0.00
1.000
0.40
100
1.000
DEF
0.00
1.000
0.40
100
1.000
DEF
0.00
1.000
GRE200 (1,2)