Download Print this page

Toshiba GR-200 Series Instruction Manual page 391

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

†Note: Although the "LED_RST_COM" signal is connected previously with several LEDs,
by the manufacturer, user can also connect the signal with the LEDs. See Chapter
3.4.4 for the way how to connect.
Operate condition
(iii)
Figure 3.4-8 shows the operate condition logic of the LEDR function, which is used to determine
a reset-condition for the operation.
Other devices traveling detected*3
Control hierarchy (e.g. 43RL) (PLC connection point) *5
528001 820701ED50
LEDR01_CTRL_RIGHT
IED serious error detected
Figure 3.4-8 Operate condition logic in LEDR
Note:
If the event "device-travelling" is detected in the CMNCTRL function, it
*3
indicates that another operator is changing the status of a device. Thus, the IED
should inhibit the operation of any device for the duration that the event is
detected. The detecting signal is denoted as "Traveling OR" in Table 3.4-1.
Note:
Criteria "unmatched conditions" are decided when the "Test-bit status" in a
*4
command is not identical to the "IED test status".
Note:
The user must program the PLC logic for "Control hierarchy condition". The
*5
user must connect that to the select condition logic using the connection point
"LEDR01_CTRL_RIGHT". For more information, see Chapter 3.3.
"LEDR01_CTRL_RIGHT" is provided in Table 3.4-2.
Settings in LED logics
3.4.4
The user can program the status and the signal of the LED, so that the LEDs are possible to
switch off upon occurrence of the reset. As shown in the logic relating to the LED†, each logic
has a timer and a setting; accordingly, setting Latch should be set for the operation of the
LEDR function. Additionally, the user should connect the signal LED_RST_CMD with the LED
logic.
†Note: For more information on LED logics, see Chapter
machine interface: LEDs
LEDR function (Function ID: 528001)
Unmatched condition detected *4
Traveling OR
Users must setup this condition correctly
SERI_ERR
[LEDDR1_EN]
On
(→p. 556).
- 372 -
1≥
&
&
*6
Technical description: Human
6F2T0200 (0.15)
To operate logic
Operate condition
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2