Download Print this page

Toshiba GR-200 Series Instruction Manual page 697

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Error LED and LCD error message
(ii)
Automatic supervision function can issues supervisor results on LEDs and LCD screen†. If the
network is connected with IEDs, they can be transferred for the remote terminals. Table 10.1-2
shows that some LEDs are used for the automatic supervision function.
Levels
0: No error
1: Serious
2: Serious (Comm.)‡
3: Minor
4: Alarm
5: Warning
Chapter User interface: Outline
†Note: See
‡Note: It depends on the degree of the communication failure.
§Note: If the "In service" has to be turned off while a minor error (level:3) is occurring, set
On for the setting [ErrorLED_cond].
The user can see current error information on Monitoring sub-menu on the LCD screen†
(see Figure 10.1-1); Table 10.1-3 shows the six detail information, which the user can examine
carefully using the hexadecimal number. When two or more errors occur at the same time, an
error code is given by the summation of the error codes. That is, when X and Y errors (e.g., X-
error-code '00000002' and Y-error-code '00000004') occur, the sum value '00000006' is screened.
CP1M(ROM/RAM) error
10:48
[Serious error]
[00000011]
[01234567]
[01234567]
Figure 10.1-1 Example error codes and detailed information on Diagnostics sub-menu
†Note: See Chap.
information is not be refreshed by itself (i.e., refresh the information manually).
Table 10.1-3 Detailed information in Hexadecimal in the ROM and the RAM error (example)
Display
area
Top row
Middle row
Bottom row
Table 10.1-2 Displays on LEDs, LCD, and SAS
"In service" LED
On
Off
On
On (Off§)
On
On
C u r r e n t e r r o r i n d i c a t e d b y S u p e r v i s i o n
1/1
C u r r e n t l o c a l t i m e ( N o t E r r o r o c c u r r i n g t i m e )
E r r o r d e g r e e ( l e v e l ) d i s p l a y e d
D e t a i l e d i n f o r m a t i o n i n H e x a d e c i m a l d u m p
[01234567]
[01234567]
[00000000]
User interface: Monitoring sub-menu: Diagnostics
Meaning of the detailed information
Left column
00000001: ROM read error
00000002: ROM RAM mismatch
RAM address
RAM value
- 678 -
"Error" LED
Error message on LCD
Off
On
On
On
Off
Off
Monitoring sub-menu
and
7 6 5 4 3 2 1 0
[
] [
"Top left"
[
] [
"Middle left"
[
] [
"Bottom left"
Right column
ROM address
ROM value
(No information displayed)
6F2T0200 (0.15)
(Not displayed)
Displayed
Displayed
Displayed
Displayed
Displayed
(→p. 865).
]
"Top right"
]
"Middle right"
]
"Bottom right"
(→p. 865). The
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2