"PLC_BIT_0201" signal, which may be used for recording events and other purposes.
5A0101 800200EF40
Figure 3.8-4 Cascading information using signal "PLC_BIT_0201"
Provision of selected status
3.8.3
Let us assume that a select-command is sent for an IED to control a target-device by the
substation automation system (SAS†), but the target-device is not ready to be controlled. The
unready condition might be due to the target-device already being in operation (e.g., CB
tripping) or a failure of the device may have occurred; thus, the IED has to drop the select-
command. If this occurs, the IED is required to send a message stating the reason to the SAS†.
Table 3.8-1 lists the messages generated in the CMNCTRL1 function describing the failure.
Table 3.8-1 Reason messages due to the release of the select-command
Signal Number
5A0001 3008001FB4
5A0001 2008001008
5A0001 2208001001
5A0001 6A08001009
5A0001 3008001FB4
†Note: The user should recognize that the reason messages are only available for
operation with the GCS1000 control system manufactured by Toshiba.
Miscellaneous settings
3.8.4
The CMNCTRL1 function has the following five common settings:
1. Control direction:
2. Return value:
3. Select-cancel timer: If the selection of a target device is made, but the control operation
4. Time out:
CMNCTRL2
function
PLC_BIT_0201
Information
cascaded§
Signal Name
SCS_CTLNUM
SCS_ORCAT
SCS_ADDCAUSE
SCS_ORIDENT
SCS_CTLNUM
The [SDCEN] can configure the control directions of the DPOS
function. If required these functions can be in the same control
direction, set On for the scheme switch [SDCEN].
When the number of the counter reaches its maximum value (in case
of the default setting, 999,999), it can return and begin
incrementing from either 0 or 1. The return number can be set with
[CNTRV].
of the selected device is not carried out in a predetermined time
limit, the selection is canceled. The time limit can be set using
[TSC]; the range is between 30 and 300sec. having a 1sec. step.
When the selection of the target device and its control execution is
- 416 -
PLC_O_BIT_0201
For
・Event record function
(5A0101 8002001F40)
・Communication (required mapping)
・LEDs
・IED screen display
・Binary output module
etc...
Description
Reason codes for the SAS†
6F2T0200 (0.15)