Toshiba GR-200 Series Instruction Manual page 105

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

SEF_MV (Function ID: 442081)
Setting items
SEF2-Rtimer
Rtimer
TSEF2R
SEF2-RTMS-
ORG
SEF2-k
SEF2-a
SEF2-c
SEF2-kr
SEF2-b
OUTPUT
SEF2-2fBlk
SEF2-VTFBlk
SEF2-UseFor
SEF2-ARCBlk
SEF3
SEF3-EN
SEF3 Directio
SEF3-Dir
n
Pol.
SEF3-Angle
SEF3-Vpol
RP
RP3-EN
RP3
SEF3 characteristic
SEF3-Timer
DT
SEF3
SEF3-DPR
TSEF3
IEC
SEF3
SEF3-DPR
SEF3-TMS-
IEC
TSEF3R
UK
SEF3
SEF3-DPR
SEF3-TMS-UK
TSEF3R
IEEE
SEF3
SEF3-DPR
SEF3-TMS-
IEEE
Rtimer
SEF3-Rtimer
TSEF3R
SEF3-RTMS-
IEEE
US
SEF3
SEF3-DPR
SEF3-TMS-US
Rtimer
SEF3-Rtimer
TSEF3R
SEF3-RTMS-
US
ORG
SEF3
SEF3-DPR
Range
Unit
DEF / DEP
- SEF2 reset delay type of ORG
0.00 - 300.00
s SEF2 definite time reset delay
SEF2 dependent reset time multiplier of
0.010 - 50.000
-
Original inverse curve
0.00000 - 500.00000
- SEF2 user original curve coefficient
0.00000 - 10.00000
- SEF2 user original curve coefficient
0.00000 - 10.00000
- SEF2 user original curve coefficient
0.00000 - 500.00000
- SEF2 user original curve coefficient
0.00000 - 10.00000
- SEF2 user original curve coefficient
Non / Block
- SEF2 operation block by 2f-detection
Non / Block
- SEF2 operation block by VTF
Trip / Alarm
- SEF2 used for trip or alarm
Non / Block
- Autoreclose block by SEF2
Off / On
- SEF3 protection enable
NonDir / Forward /
- SEF3 selection of protection direction
Reverse
-90 - 90
deg SEF3 polarizing angle in directional element
3.0
V SEF3 polarizing vol. in directional element
Off / On
- Enabling RP in directional protection
0.00 – 100.00
W Threshold of residual power element
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- SEF3 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.001 - 1.000
A SEF3 threshold (in DT mode)
10 - 100
% SEF3 drop-out/pick-up ratio
0.00 - 300.00
s SEF3 operating delay time (in DT mode)
0.001 - 1.000
A SEF3 threshold (in IDMT mode)
10 - 100
% SEF3 drop-out/pick-up ratio
0.010 - 50.000
- SEF3 time multiplier of IEC inverse curve
0.00 - 300.00
s SEF3 definite time reset delay
0.001 - 1.000
A SEF3 threshold (in IDMT mode)
10 - 100
% SEF3 drop-out/pick-up ratio
0.010 - 50.000
- SEF3 time multiplier of UK inverse curve
0.00 - 300.00
s SEF3 definite time reset delay
0.001 - 1.000
A SEF3 threshold (in IDMT mode)
10 - 100
% SEF3 drop-out/pick-up ratio
0.010 - 50.000
- SEF3 time multiplier of IEEE inverse curve
DEF / DEP
- SEF3 reset delay type of IEEE
0.00 - 300.00
s SEF3 definite time reset delay
SEF3 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.001 - 1.000
A SEF3 threshold (in IDMT mode)
10 - 100
% SEF3 drop-out/pick-up ratio
0.010 - 50.000
- SEF3 time multiplier of US inverse curve
DEF / DEP
- SEF3 reset delay type of US
0.00 - 300.00
s SEF3 definite time reset delay
SEF3 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.001 - 1.000
A SEF3 threshold (in IDMT mode)
10 - 100
% SEF3 drop-out/pick-up ratio
- 86 -
Contents
6F2T0200 (0.15)
Default
Note
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
Trip
Block
Off
Non
-45
3.0
Off
0.00
DT
0.010
100
1.00
0.010
100
1.000
0.00
0.010
100
1.000
0.00
0.010
100
1.000
DEF
0.00
1.000
0.010
100
1.000
DEF
0.00
1.000
0.010
100
GRE200 (1,2)