Toshiba GR-200 Series Instruction Manual page 423

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Object_reference
System/LLN0$Mod$origin
System/LLN0$Mod$origin
System/LLN0$Mod
Figure 3.6-4 orCat attribute mapped into MOD object of LLNO
Mapping input data
(iii)
The MDCTRL01 function can receive three commands "select, operate, and cancel. Thus, the
user should map the input-point "MDCTRL01 _CONTROL_REQ". Table 3.6-4 shows the input-
point " MDCTRL01 _CONTROL_REQ" and the Object reference "System/LLN0$Mod$" ; the user
should map the Object reference having attributes CO and CF in FC to the input-point . Note that
the user should map the input-point to all attributes having CO and CF . Figure below shows
how to map a signal.
Table 3.6-3 Mapping signals for MOD object.
Attribute
Type
orCat
orCategory
orIdent
Octet64
stSeld
BOOLEAN
- 404 -
FC
Signal Number
ST
5500013013011000
ST
5500016A13011009
ST
5500010013011D90
6F2T0200 (0.15)
Signal Name
MDCTRL01_ORCAT
MDCTRL01_ORIDENT
MDCTRL01_SLD_RPT
Drag and drop
GRE200 (1,2)