SEF1 element in the forward characteristic
Non-operation zone
o
Ie
SEF1-EN
RP1 element in the forward characteristic
Non-operation zone
o
Ie
RP1
SEF1-DIR
Figure 2.4-6 Forward characteristic (45°) restrained by setting [RP1]=2 watt
Note: If the reverse characteristic is required in the SEF1 and PR1 elements, set [SEF1-
DIR]=Reverse so that a reverse one will be obtained. RP1 operation signal can be
found at signal monitoring point 'RP1R' during that time.
Note: RP1 operation will be canceled by undervoltage (RP-UVBLK) and undercurrent
(RP-UCBLK) elements, when the input signals are not obtained sufficiently (i.e.,
Ve and Ie are less than 0.5V and 0.001A). For more information, see Chapter
Technical description: Transformer module for AC analog input
The RP element will be characterized by Watt metric setting; hence, a value, which is ruled by
the scalar product of an entering current (Ie) and applied voltage (Ve), should be set for the
setting [RP1].
Setting of standby earth-fault
2.4.7
In which case the residual current is injected from the neutral circuit at the lower side of a
transformer, the standby earth-fault protection can trip the CB located at the lower side of the
transformer; the trip command is issued by the SEF1 element, but issuing is retarded by
setting [TSEF1S2] compared with the original SEF1 issuing. The user should set On for the
scheme switch [SEF1S2-EN]†.
†Note: The standby earth-fault protection is only available for the SEF1 element.
Scheme logic
2.4.8
The scheme logic for both the non-directional and the directional SEF1 element is illustrated
Margin=2.5° (fixed)
Operation zone
SEF-Vpol (Ve180°)
Setting [SEF1-Angle] = -45°
8000011C23
Angle line
SEF1
On
Setting [RP1] = 2 watt
Operation zone
SEF-Vpol (Ve180°)
Setting [SEF1-Angle] = -45°
8000011C60
Angle line
RP1F
On
Off
Forward
- 81 -
TSEF1
t
0
&
&
0.00-300.00s
&
≥1
&
6F2T0200 (0.15)
8000011B60
SEF1-OPT
(→p. 510).