10.2.32 Supervision of GOOSE publishing (LAN(GOOSE)error)
Publishing error in the IEC 61850 communication† is detected when a GOOSE message is not
received.
†Note: see Chapter
Error level
(i)
Error level has been set at level 3 (Minor error; default), but the user can change it with setting
[CHK_GOOSERCV:LVl].
[CHK_GOOSERCV:Sw]. Detecting the error will be presented in five-minutes if the IED
detects no reception of GOOSE. When the IED starts to receive the GOOSE, the error will be
reset in one-minute.
Error message
(ii)
When detecting an error, the error message will be shown on LCD screen. LED will be lit up.
Table 10.2-64 Error messages provided by the supervisor in CHK_GOOSERCV
Message and level
LAN(GOOSE) error
Error level
Table 10.2-65 Detailed information in Hexadecimal in CHK_GOOSERCV
Display
area
Top
Receipt state regarding to the GOOSE
row
subscribe information#1†
Middle
Receipt state regarding to the GOOSE
row
subscribe information#3†
Bottom
Receipt state regarding to the GOOSE
row
subscribe information#5†
†Note: "c000" is shown when no reception.
Communication protocol: IEC 61850 communication
Remember
that
Meaning of the information
Detection of the failure in GOOSE
Minor error (Level 3)
Meaning of the detailed information
Left column
- 713 -
the
user
needs
to
Right column
Receipt state regarding to the GOOSE
subscribe information#2†
Receipt state regarding to the GOOSE
subscribe information#4†
Receipt state regarding to the GOOSE
subscribe information#6†
6F2T0200 (0.15)
(→p. 751).
set
for
setting
On
GRE200 (1,2)