IEC 60870-5-103 communication
The IEC 60870-5-103 standard is one of the communication protocols when measuring data is
required to communicate between the control system and an IED. The communication is
carried out with RS485 or Fiber optic interface†. The data, measured and status, is transferred
over the IEC 60870-5-103 communication. The user has to make the configuration of the IEC
60870-5-103 with GR-TIEMS engineering. See
Measured data: current, voltage, active power, reactive power, frequency
Status data:
†Note: Selecting a communication module (interface) is dependent on the ordering about
the hardware selection. With regard to the communication specification, see
Chapter
(→page 528).
Selection of IEC60870-5-103 protocol
11.5.1
Figure 11.5-1 shows the selection menu of a slave protocol. The user should set IEC103 for the
[Slave Protocol] if the IED has to communicate in the IEC60870-5-103. Note that the user has
to restart the IED (i.e., the user has to turns it off, and on) after switching a protocol from the
other.
Communication
10:48
1/7
LAN
USBCOM
RS485
SLAVE PROTOCOL
IEC61850
IEC103 SLV
MODBUS
Figure 11.5-1 Selection of IEC103 on commination setting menu
Note: This sample menu illustrates how to select the IEC103, so that we discuss neither
the inclusion of IEC61850, DNP3.0, and Modbus nor the selection of those
protocols here. See Figure 11.1-1 to check the inclusion of the protocols in the IED.
The slave operation can be switched off briefly if the setting [103BLK] = On.
Communication
10:48
1/7
LAN
USBCOM
RS485
SLAVE PROTOCOL
IEC61850
IEC103 SLV
Figure 11.5-2 Canceling the IEC103 operation (LCD setting menu)
events, fault indications, etc.
Technical description: Signal processing and communication module
SLAVE PROTOCOL
10:48
>
Slave Protocol
>
IEC103
>
>
>
>
>
IEC103 SLV
10:48
>
103ADDR
>
>
103TST
>
Off
>
103BLK
>
Off (➔On)
- 819 -
Chapter Engineering tool
SLAVE PROTOCOL
1/1
10:48
+
1/3
+
2
Press
+
+
Press
set [103BLK]=On
6F2T0200 (0.15)
(→p. 585):
1/4
IEC61850†
IEC103
DNP3.0†
Modbus†
ENTER
key
, , ,  to
GRE200 (1,2)