10.2.11 Supervision of setting data (Setting error)
Setting values are checked every second. An error message is displayed when the incorrect
value is found.
Error level
(i)
The error level has been set at level 1 (Serious error) in the automatic supervision. The
detection is carried out periodically. If an error is detected, the IED does not restart the
operation automatically. It runs for the memorized settings at CPU module
incorrect setting is removed, the error messages will be cleared in a second.
Note: It is discussed in Chapter
1
communication module
Error message
(ii)
When detecting an error, the error message can be shown on the LCD screen. LED will be lit
up.
Table 10.2-21 Error messages provided by the supervisor in CHK_SETTING
Message and level
CP*_ (Setting) error
Error level
Table 10.2-22 Detailed information expressed in Hexadecimal in CHK_SETTING
Display
area
00000001: Failure exists in the common settings
Top
00000002: Failure exists in the group setting
row
00000004: Error data found in the setting table
Middle
Offset address corresponding to the failure in
row
the group setting
Bottom
(No information is displayed)
row
Technical description: Signal processing and
(→p. 528)
Meaning of the information
Setting error detected on the following module instructed with
"CP*_" as follows:
CP1M:
CPU module
Serious error (Level 1)
Meaning of the detailed information
Left column
- 690 -
.
Offset address corresponding to
the failure in the common settings
Error information about the
(No information is displayed)
6F2T0200 (0.15)
. When the
1
Right column
setting table
GRE200 (1,2)