IEC 61850 configuration files
(iii)
Substation configuration language (SCL) files are generated by the configuration in the IEC
61850 protocol. The SCL files are used to exchange the configuration data in different
manufacture tools. Two types of files are used for exchanging data in Table 11.3-5.
SCL file
.ICD
IED Capability Description
.CID
Configured IED Description
Exporting and Importing CID/ICD file
The user can export or / import a CID/ICD file as a CSV file. The user can edit
the exported CSV file using the MS-EXCEL®; the user can import the edited CSV
file back to the GR-TIEMS. Figure 11.3-10 shows the options available to
import/export CID/ICD file. The user can either click the icons on the menu bar
or select the required option form the File menu drop down list.
Manage third party CID file
The GR-TIEMS can have third party CID file. In the project tree of the GR-TIEMS,
the user can use the device information for creating a third Party IED. To
configure dataset, RCB, GCB, GOOSE publish and GOOSE subscribe settings
and so on, the data attributes are used after the creation of the data.
Mapping application data in IEC 61850
For any IED, the IEC61850 configuration* is available by default. The user
Table 11.3-5 Types of SCL files
This file describes the capabilities of an IED. It contains the
communication data and function of LN in an IED.
Every device configured for IEC 61850 in the GR-TIEMS tool
generates a CID file. This file is then written to the IED. This
file contains configuration information of the IED to which it is
connected.
Import CID/ICD
Export CID
Export ICD
Figure 11.3-10 Export / Import of CID / ICD file