Figure 4.1-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time B). This is because the function can count the iterative number of
incoming signals. Detection commences at Time 'A', the setting [DPOS-NELD] is provided so
that the suppression commences at Time 'B'. The setting [DPOS-TELD] pertains to the
operation of the detection function from Time 'A' (e.g., Time 'A' to Time 'C').
The event suppression ceases when the iterative signals stop. The user can adjust the
point at which event suppression stops using the setting [DPOS-TELR]; as a result, no
suppressed signal is output after the end of the iterative signals (e.g., Time 'D' to Time 'E').
To initiate the event suppression the user should set On for scheme switch [DPOS01-
SPPEN].
BO connection for "Select command On/Off"
(ii)
Figure 4.1-43 exemplifies the connection for the select command On and Off. Suppose that
connection with the BOs is achieved by the PLC function using connection points
"DPOS01_OSL_BO_FLG" and "DPOS01_FSL_BO_FLG"†; as a result, the "Select command
On" and the "Select command Off" signals are issued at BO1 and BO2 respectively.
Select logic in DPOS01
Select logic for select command On
in DPOS01
Select logic for select command
Off in DPOS01
Figure 4.1-43 Example of select commands connected with BO1 & BO2 at IO#1-2
†Note: Table 4.1-8 shows the remaining signals with the exception of
" DPOS01_OSL_BO_FLG "
(512001 8603011DC6)
To contact health
check
Connected by
"Programming"
PLC connection point on BO1
" DPOS01_FSL_BO_FLG "
(512001 8A03011DC4)
To contact health
check
Connected by
"Programming"
PLC connection point on BO2
- 473 -
BO1 circuit at IO#1-2 (Function ID: 200B41)
Signal captured by
≥1
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[BO1_CPL]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
200B41 310200E11D
BO1_SOURCE
BO2 circuit at IO#1-2 (Function ID: 200B41)
Signal captured by
≥1
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[BO2_CPL]
[Input signal 4]
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
200B41 310201E11D
BO2_SOURCE
6F2T0200 (0.15)
Terminal and
wire
" BO1 "
Select
command
( 200B41_8002001112)
On to the
device
DRIVER
BO1
&
≥1
" BO1-RB "
On
&
(200B41_8002001113)
Off
To contact health
check
Terminal and
wire
Select
" BO2 "
command
( 200B41_8102011112)
Off to the
device
DRIVER
BO2
&
≥1
" BO2-RB "
On
&
(200B41_8102011113)
Off
To contact health
check
GRE200 (1,2)

Advertisement

loading