Setting
2.6.4
UC_MV (Function ID: 450081)
Setting items
UC1-EN
UC2-EN
UC1
UC1
TUC1
Output
UC1-CTFBlk
UC1-UseFor
UC2
UC2
TUC2
Output
UC2-CTFBlk
UC2-UseFor
Range
Unit
Off / On
- UC1 protection enable
Off / On
- UC2 protection enable
0.10 - 10.00
A UC1 threshold
0.00 - 300.00
s UC1 operating delay time
Non / Block
- UC1 operation block by CTF
Trip / Alarm
- UC1 used for trip or alarm
0.10 - 10.00
A UC2 threshold
0.00 - 300.00
s UC2 operating delay time
Non / Block
- UC2 operation block by CTF
Trip / Alarm
- UC2 used for trip or alarm
- 112 -
Contents
6F2T0200 (0.15)
Default
Note
Off
Off
0.20
1.00
Non
Trip
0.20
1.00
Non
Trip