Toshiba GR-200 Series Instruction Manual page 279

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Connection points in PLC logic
ARCD_MV (Function ID: 4A70081)
Element ID
800000EBB0
810000EBB1
800000EBB2
800000EBB3
800000EBB4
800000EBB5
800000EBB6
810000EBB7
810000EBB8
810000EBB9
820000EBBA
830000EBBB
840000EBBC
800000EBBD
800000EBBE
Mapping point in IEC 61850
ARCD_MV (Function ID: 4A7081)
Element ID
3000001B7D
)
Name
Description
ARC-OFF
Request to select Off mode in ARC
ARC-ON
Request to select On mode in ARC
EXT.ARC_START
Receipt point from an external relay for starting ARC
ARC NO ACT
Request not to operate
CB-ARC READY
Signal injection point indicating that the CB is ready to be reclosed
ARC_MAIN_START
Start signal for the ARC operation
ARC_MAIN_COND
Point for the permissive signal to issue the first ARC shot
ARC_SUB_START
Sub-start signal for the ARC operation
ARC_SUB_COND
Point for the sub permissive signal to issue the first ARC shot
ARC-S2 COND
Point for the permissive signal to issue the second ARC shot
ARC-S3 COND
Point for the permissive signal to issue the third ARC shot
ARC-S4 COND
Point for the permissive signal to issue the fourth ARC shot
ARC-S5 COND
Point for the permissive signal to issue the fifth ARC shot
CB_MANUAL_CLOSE
Point for reclose signal generated manually
ARC_BLOCK
Point for blocking the ARC operation
Name
Description
ARC_AUTORECST
AutoRecSt signal in RREC of IEC61850 LN
- 260 -
6F2T0200 (0.15)
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2