Advertisement

Setting
2.25.5
VCHK_MV (Function ID:4A8081)
Setting items
ARC-VCHK-
EN
VCHK
SYN-Vbus
SYN-Vline
VCHK-OVB
VCHK-UVB
VCHK-OVL
VCHK-UVL
OVLL
SYN-Angle
SYN-dV
df
SYN-df
SYN-df
ARC-LB_DL
ARC-DB_LL
ARC-DB_DL
ARC-SYN
ARC-NOVCHK
Time
T_LB_DL
T_DB_LL
T_DB_DL
T_SYN
T_OVL3P
Range
Unit
Off / On
- VCHK enabling switch
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
- Running Voltage
Vs
V-L1 / V-L2 / V-L3 / V-
L12 / V-L23 / V-L31 /
- Incoming Voltage
Vs
10 - 150
V Voltage for the checking Live-Bus
10 - 150
V Voltage for the checking Dead-Bus
10 - 150
V Voltage for the checking Live-Line
10 - 150
V Voltage for the checking Dead-Line
10 - 150
V Voltage for the checking 3phase Live-line
0 - 75
deg Difference angle for the checking SYN
0 - 150
V Difference voltage for the checking SYN
Switch for the checking SYN for difference
Off / On
-
frequency
0.01 - 2.00
Hz Difference frequency for the checking SYN
Voltage check Live-Bus & Dead-Line is
Off / On
-
applied to ARC
Voltage check Dead-Bus & Live-Line is
Off / On
-
applied to ARC
Voltage check Dead-Bus & Dead-Line is
Off / On
-
applied to ARC
Off / On
- Voltage check SYN is applied to ARC
Off / On
- Voltage check is not applied to ARC
0.01 - 100.00
s Voltage check time Live-Bus and Dead-Line
0.01 - 100.00
s Voltage check time Dead-Bus and Live-Line
0.01 - 100.00
s Voltage check time Dead-Bus and Dead-Line
0.01 - 100.00
s Voltage check time SYN1
0.01 - 100.00
s Voltage check time 3phase Live-line
- 292 -
Contents
6F2T0200 (0.15)
Default
Note
Off
Vs
V-L1
51
13
51
13
51
30
150
Off
1.00
Off
Off
Off
Off
On
0.05
0.05
0.05
1.00
0.05
GRE200 (1,2)