Download Print this page

Toshiba GR-200 Series Instruction Manual page 373

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting
2.29.3
REVPOW_MV (Function ID: 4C0081)
Setting items
RP
RP-Power
RP-UVBlk
UV-RPBLK
RP1
RP1-EN
RP1
RP1-DPR
TRP1
O RP1-CBBlk
u TRP1-CB
t
RP1-2fBlk
p
RP1-VTFBlk
u RP1-CTFBlk
t
RP1-UseFor
RP2
RP2-EN
RP2
RP2-DPR
TRP2
O RP2-CBBlk
u TRP2-CB
t
RP2-2fBlk
p
RP2-VTFBlk
u RP2-CTFBlk
t
RP2-UseFor
RQ
RQ-Current
RQ-UVBlk
UV-RQBLK
RQ1
RQ1-EN
RQ1
RQ1-DPR
TRQ1
O RQ1-CBBlk
u TRQ1-CB
t
RQ1-2fBlk
p
RQ1-VTFBlk
u RQ1-CTFBlk
t
RQ1-UseFor
RQ2
RQ2-EN
RQ2
RQ2-DPR
TRQ2
O RQ2-CBBlk
u TRQ2-CB
t
RQ2-2fBlk
p
RQ2-VTFBlk
u RQ1-CTFBlk
t
RQ2-UseFor
Range
Unit
DEP / Send / Receive
-
Non / Block
-
5.0 - 100.0
V
Off / On
-
-1500.0 - -5.0
W
50 - 98
%
0.00 - 300.00
s
Non / Block
-
0.00 - 300.00
s
Non / Block
-
Non / Block
-
Non / Block
-
Trip / Alarm
-
Off / On
-
-1500.0 - -5.0
W
50 - 98
%
0.00 - 300.00
s
Non / Block
-
0.00 - 300.00
s
Non / Block
-
Non / Block
-
Non / Block
-
Trip / Alarm
-
DEP / Lead / Lag
-
Non / Block
-
5.0 - 100.0
V
Off / On
-
-1500.0 - -5.0
var RQ1 threshold
50 - 98
%
0.00 - 300.00
s
Non / Block
-
0.00 - 300.00
s
Non / Block
-
Non / Block
-
Non / Block
-
Trip / Alarm
-
Off / On
-
-1500.0 - -5.0
var RQ2 threshold
50 - 98
%
0.00 - 300.00
s
Non / Block
-
0.00 - 300.00
s
Non / Block
-
Non / Block
-
Non / Block
-
Trip / Alarm
-
- 354 -
Contents
Power direction definition
UV block function enable
UV block threshold
RP1 protection enable
RP1 threshold
RP1 drop-out/pick-up ratio
RP1 operating delay time
RP1 operation blocking by CB closed
Confirmation time to CB closed
RP1 operation blocking by 2f-
detection
RP1 operation blocking by VTF
RP1 operation blocking by CTF
RP1 used for trip or alarm
RP2 protection enable
RP2 threshold
RP2 drop-out/pick-up ratio
RP2 operating delay time
RP2 operation blocking by CB closed
Confirmation time to CB closed
RP2 operation blocking by 2f-
detection
RP2 operation blocking by VTF
RP2 operation blocking by CTF
RP2 used for trip or alarm
Power direction definition
UV block function enable
UV block threshold
RQ1 protection enable
RQ1 drop-out/pick-up ratio
RQ1 operating delay time
RQ1 operation blocking by CB closed
Confirmation time to CB closed
RQ1 operation blocking by 2f-
detection
RQ1 operation blocking by VTF
RQ1 operation blocking by CTF
RQ1 used for trip or alarm
RQ2 protection enable
RQ2 drop-out/pick-up ratio
RQ2 operating delay time
RQ2 operation blocking by CB closed
Confirmation time to CB closed
RQ2 operation blocking by 2f-
detection
RQ2 operation blocking by VTF
RQ1 operation blocking by CTF
RQ2 used for trip or alarm
6F2T0200 (0.15)
Default
Note
Send
Non
5.0
Off
-30.0
95
0.00
Block
5.00
Non
Non
Non
Trip
Off
-30.0
95
0.00
Block
5.00
Non
Non
Non
Alarm
DEP
Non
5.0
Off
-30.0
95
0.00
Block
5.00
Non
Non
Non
Trip
Off
-30.0
95
0.00
Block
5.00
Non
Non
Non
Alarm
GRE200 (1,2)

Advertisement

loading

This manual is also suitable for:

Gre200-1Gre200-2