Toshiba GR-200 Series Instruction Manual page 633

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setup for the fault recorder
8.1.3
Operation identifiers (ID1–ID128)
(i)
The user can select the operation identifies arbitrarily using the settings [OP Mode ID1] etc.
For example, when the operation result with regard to the overcurrent relay element (i.e., OC1
in phase-A) shall be recorded, choose the operated signal 'OC1-OPT-A (440081 800011B68)"
and set it for the [OP Mode ID1]. Remember to program the displaying name about the OC1-
OPT-A using the setting [OP Mode Name1] (e.g., "OC1-A relay OP-ed"). Note that the length
of the displaying name should be less than 18 letters. The user should find blanks in the setting
list, because several IDs have been already set.
Logical signals (ID201–ID264)
(ii)
Wishing to record a logical level '1 (TRUE)' or '0 (FALSE)' on the circuits, the user can pick the
logical signal using settings the [OP Mode ID265] etc. For example, the user wishes to recode
the output level of the binary input circuit#1 (BO1) at the IO#1 slot, set its PLC monitoring
point '200B41 8002001112' for the setting [OP Mode ID265]; set the displaying name using the
[OP Mode Name265].
Additional triggers for the recording
(iii)
Wishing to start the fault recorder except for the trip instruction, the user can use the PLC
connection points 'ADD_F.RECORD_TRIG1' to 'ADD_F.RECORD_TRIG4', respectively.
Time setting for Pre-fault
(iv)
The instant before the trip is programmable using the setting [Pre-Fault Time] among 10s, 50s,
100s, 200s, 300s.
Unit setting for the quantities
(v)
To change the units of power quantities, go to the metering function discussed in
Monitoring function
(→p. 655).
- 614 -
6F2T0200 (0.15)