5.4.9
Parameter write selection
Whether to enable the writing to various parameters or not can be selected. Use this function to prevent parameter values from
being rewritten by misoperation.
Pr.
77
Parameter write selection
E400
• Pr.77 can be set at any time regardless of the operation mode or operation status. (Setting through communication is
unavailable.)
 Writing parameters only during stop (Pr.77 = "0" initial value)
• Parameters can be written only during a stop in the PU operation mode.
• The following parameters can always be written regardless of the operation mode or operation status.
Pr.
4 to 6
(Multi-speed setting high-speed, middle-speed,
low-speed)
22
Stall prevention operation level
24 to 27
(Multi-speed setting speed 4 to speed 7)
52
Operation panel main monitor selection
54
CA terminal function selection
55
Frequency monitoring reference
56
Current monitoring reference
PWM frequency selection
*1
72
75
Reset selection/disconnected PU detection/PU
stop selection
77
Parameter write selection
Operation mode selection
*2
79
129
PID proportional band
130
PID integral time
133
PID action set point
134
PID differential time
158
AM terminal function selection
160
User group read selection
232 to 239
(Multi-speed setting speed 8 to speed 15)
Soft-PWM operation selection
*1
240
241
Analog input display unit switchover
268
Monitor decimal digits selection
290
Monitor negative output selection
296, 297
(Password setting)
306
Analog output signal selection
310
Analog meter voltage output selection
Communication startup mode selection
*2
340
345, 346
(DeviceNet communication)
416, 417
(PLC function)
434, 435
(CC-Link communication)
496, 497
(Remote output)
498
PLC function flash memory clear
*2
NET mode operation command source selection
550
*1
Writing during operation is enabled in PU operation mode, but disabled in External operation mode.
*2
Writing during operation is disabled. To change the parameter setting value, stop the operation.
168
5. PARAMETERS
5.4 (E) Environment setting parameters
Name
Initial value
0
Name
Setting range
0
Writing is enabled only during stop.
1
Parameter writing is disabled.
2
Parameter writing is enabled in any operation
mode regardless of the operation status.
Pr.
PU mode operation command source selection
*2
551
555 to 557
(Current average value monitor)
656 to 659
(Analog remote output)
663
Control circuit temperature signal output level
675
User parameter auto storage function selection
755 to 758
(Second PID control)
759
PID unit selection
774 to 776
(PU/DU monitor selection)
866
Torque monitoring reference
888, 889
(Free parameter)
891 to 899
(Energy saving monitor)
900
CA terminal calibration
901
AM terminal calibration
930
Current output bias signal
930
Current output bias current
931
Current output gain signal
931
Current output gain current
990
PU buzzer control
991
PU contrast adjustment
997
Fault initiation
*2
PM parameter initialization
998
Automatic parameter setting
*2
999
1000
Direct setting selection
1006
Clock (year)
1007
Clock (month, day)
1008
Clock (hour, minute)
1019
Analog meter voltage negative output selection
1142
Second PID unit selection
1150 to 1199
(PLC function user parameters)
1211 to 1219
(PID gain tuning)
1460 to 1466
(PID multistage set points 1 to 7)
1480 to 1485
(Load characteristics fault detection)
Description
Name