 Switching operation mode by external signal (X16 signal)
• When External operation and the operation from the operation panel are used together, the PU operation mode and
External operation mode can be switched during a stop (during motor stop, start command OFF) by using the PU-External
operation switchover signal (X16).
• When Pr.79="0", "6" or "7", switching between the PU operation mode and External operation mode is possible. (When
Pr.79="6", the switchover can also be made during operation.)
• To input the X16 signal, set "16" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function to
a terminal.
Pr.79
X16 signal status and operation mode
setting
ON (External)
0 (initial value)
External operation
mode
1
PU operation mode
2
External operation mode
3, 4
External/PU combined operation mode
6
External operation
mode
7
X12 (MRS)
External operation
ON
mode
X12 (MRS)
External operation mode
OFF
NOTE
• The status of the operation mode follows the Pr.340 Communication startup mode selection setting and the ON/OFF
state of the X65 and X66 signals. (For details, refer to
• The priority among Pr.79 and Pr.340 and signals is Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
 Switching the operation mode by external signals (X65, X66 signals)
• When Pr.79 ="0, 2 or 6", the PU operation mode and External operation modes can be changed to the Network operation
mode during a stop (during motor stop, start command OFF) by the PU/NET operation switchover (X65) signal, the
External/NET operation switchover (X66) signal. (When Pr.79 = "6", switchover is enabled during operation.)
• To switch between the Network operation mode and the PU operation mode
1.
Set Pr.79 = "0 (initial value) or 6".
2.
Set Pr.340 Communication startup mode selection = "10 or 12".
3.
Set "65" in any of Pr.178 to Pr.189 to assign the PU/NET operation switchover (X65) signal to a terminal.
4.
When the X65 signal is ON, the PU operation mode is selected. When the X65 signal is OFF, the Network
operation mode is selected.
Pr.340
Pr.79
setting
setting
10, 12
0 (initial value)
1
2
3, 4
6
7
X12 (MRS)
ON
X12 (MRS)
OFF
OFF (PU)
PU operation mode
Switching among the External, PU, and NET operation modes is
enabled.
PU operation mode fixed
External operation mode fixed. (Switching to NET operation mode is
enabled.)
External/PU combined operation mode fixed
PU operation mode
Switching among the External, PU, and NET operation mode is
enabled while running.
PU operation mode
Switching among the External, PU, and NET operation mode is
enabled. (In the External operation mode, output shutoff.)
External operation mode fixed. (Forcibly switched to External
operation mode.)
page
X65 signal state
ON (PU)
OFF (NET)
PU operation mode
NET operation mode
PU operation mode
NET operation mode
External/PU combined operation mode
PU operation mode
NET operation mode
Switching between the External operation
mode and PU operation mode is enabled.
External operation mode
Remarks
211.)
PU operation mode fixed
NET operation mode fixed
External/PU combined operation mode fixed
Switching between operation modes is enabled
while running.
Output is shutoff in the External operation mode.
The operation mode is forcibly switched to the
External operation mode.
5.6 (D) Operation command and frequency command
Remarks
211
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10