5.12

(N) Operation via communication and its settings

Purpose
To start operation via
communication
To operate via communication
from PU connector
To operate via communication
from RS-485 terminals
To Communicate using USB (FR
Configurator2)
To connect a GOT
To back up the data of parameter
settings and PLC function to the
GOT
5.12.1
Wiring and configuration of PU connector
Using the PU connector enables communication operation from a personal computer, etc.
When the PU connector is connected with a personal, FA or other computer by a communication cable, a user program can
run and monitor the inverter or read and write to parameters.
 PU connector pin-outs
Pin number
Name
1
SG
2
3
RDA
4
SDB
5
SDA
6
RDB
7
SG
8
Initial setting of operation via
communication
Initial setting of computer link
communication (PU connector)
Initial setting of computer link
communication (RS-485 terminals)
MODBUS RTU communication
specification
BACnet MS/TP protocol
USB communication
GOT automatic recognition
Backup/restore
Description
Earth (ground) (connected to terminal 5)
Operation panel power supply
Inverter receive+
Inverter send-
Inverter send+
Inverter receive-
Earth (ground) (connected to terminal 5)
Operation panel power supply
Parameter to set
P.N000, P.N001,
P.N013, P.N014
P.N020 to P.N028
P.N030 to P.N038
P.N002, P.N030,
P.N031, P.N033,
P.N034, P.N080
P.N030, P.N031,
P.N050 to P.N054
P.N040, P.N041
P.N020, P.N030
P.N110, P.N111
Inverter
(Receptacle side)
Front view
8
to
1
5.12 (N) Operation via communication and its settings
Refer to
page
Pr.549, Pr.342,
478
Pr.502, Pr.779
Pr.117 to Pr.124
483
Pr.331 to Pr.337,
Pr.341
Pr.539, Pr.331 to
500
Pr.334, Pr.343
Pr.331, Pr.332,
516
Pr.390, Pr.726 to
Pr.729
Pr.547, Pr.548
532
Pr.117, Pr.331
533
Pr.434, Pr.435
535
5. PARAMETERS
3
4
5
5
5
6
7
8
9
10
473