 Mailbox parameter / Mailbox value (BACnet registers)
• Access to the properties which are not defined as objects are available by using "Mailbox parameter" and "Mailbox value".
• To read a property, write the register of the intended property to "Mailbox parameter", and then read "Mailbox value". To
write a property, write the register of the intended property to "Mailbox parameter", and then write a value to "Mailbox
value".
• System environment variable
Register
40010
Operation mode / inverter setting
• Operation mode / inverter setting
Mode
Read value
EXT
H0000
PU
H0001
EXT
H0002
JOG
PU
H0003
JOG
NET
H0004
PU +
H0005
EXT
*1
Writing is available depending on the Pr.79 and Pr.340 settings. For the details, refer to
The restrictions depending on the operation mode changes according to the computer link specifications.
• Real time monitor
The register numbers and the monitor items are the same as those of the MODBUS RTU real time monitor. Refer to the
MODBUS RTU real time monitor on
• Parameter
Pr.
Register
0 to 999
41000 to
41999
902
41902
902
42092
43902
125 (903) 41903
903
42093
43903
904
41904
904
42094
43904
126 (905) 41905
905
42095
43905
917
41917
917
42107
43917
918
41918
526
5. PARAMETERS
5.12 (N) Operation via communication and its settings
Definition
Read/write
Read/write
Write value
*1
H0010
*1
H0011
-
-
H0014
-
page
274.
Parameter name
Refer to the parameter list
(page
for parameter names.
Terminal 2 frequency setting bias
(frequency)
Terminal 2 frequency setting bias
(analog value)
Terminal 2 frequency setting bias
(terminal analog value)
Terminal 2 frequency setting gain
(frequency)
Terminal 2 frequency setting gain
(analog value)
Terminal 2 frequency setting gain
(terminal analog value)
Terminal 4 frequency setting bias
(frequency)
Terminal 4 frequency setting bias
(analog value)
Terminal 4 frequency setting bias
(terminal analog value)
Terminal 4 frequency setting gain
(frequency)
Terminal 4 frequency setting gain
(analog value)
Terminal 4 frequency setting gain
(terminal analog value)
Terminal 1 bias frequency (speed)
Terminal 1 bias (speed)
Terminal 1 bias (speed) (terminal
analog value)
Terminal 1 gain frequency (speed)
For write, set data as the operation mode setting.
For read, data is read as the operation mode status.
Read/write
108)
Read/write
The parameter number + 41000 is the register number.
Read/write
Read/write
Analog value (%) set to Pr.902
Read
Analog value (%) of the voltage (current) applied to the
terminal 2
Read/write
Read/write
Analog value (%) set to Pr.903
Read
Analog value (%) of the voltage (current) applied to the
terminal 2
Read/write
Read/write
Analog value (%) set to Pr.904
Read
Analog value (%) of the current (voltage) applied to the
terminal 4
Read/write
Read/write
Analog value (%) set to Pr.905
Read
Analog value (%) of the current (voltage) applied to the
terminal 4
Read/write
Read/write
Analog value (%) set to Pr.917
Read
Analog value (%) of the voltage applied to the terminal 1
Read/write
Remarks