Mitsubishi Electric 800 Series Instruction Manual page 383

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• Example of operation sequence with automatic bypass sequence (Pr.139  "9999", Pr.159  "9999")
ON
STF
OFF
Output frequency Pr.139
Frequency command
Actual motor speed
INV
ON
MC3
operation
OFF
Commercial
ON
MC2
power supply
OFF
operation
A : Pr.136 MC switchover interlock time
C : Pr.57 Restart coasting time
Operating procedure
• Operation flowchart
Power supply ON
Setting the parameters
Start inverter operation
Constant-speed commercial
power supply operation
Deceleration (stop)
inverter operation
• Signal operation after setting parameters
Status
Power ON
OFF
(OFF)
At start (Inverter)
OFFON
During constant-
ON
speed operation
(commercial power
supply)
For deceleration,
ON
switched to the
inverter operation
(inverter)
Stop
ON
382
5. PARAMETERS
5.11 (A) Application parameters
C
A
B : Pr.137 Start waiting time
D : Pr.58 Restart cushion time
• Pr.135 = "1"
• Pr.136 = "2.0 s"
• Pr.137 = "1.0 s" (Set the time until MC3 is actually turned ON and the inverter and
motor are electrically connected. If the time is short, the restart may not function
properly.)
• Pr.57 = "0.5 s"
• Pr.58 = "0.5 s" (Always set this to switchover from the commercial power supply
operation to the inverter operation.)
MRS
CS
STF
OFF
OFF
(OFF)
(OFF)
OFFON
OFFON
ONOFF
ON
OFFON
ON
ON
ONOFF
Pr.159
A
B
C
D
A
MC1
MC2
OFFON
OFF
(OFFON)
(OFF)
ON
OFF
ON
OFFON
ON
ONOFF
ON
OFF
Time
A
B
C
D
MC3
Remarks
OFFON
External operation mode
(OFFON)
(PU operation mode)
ON
ONOFF
MC2 turns ON after MC3
turns OFF.
Waiting time is 2 s (while
coasting).
OFFON
MC3 turns ON after MC2
turns OFF.
Waiting time is 4 s (while
coasting).
ON
Time