 Fault output after deceleration to stop (Pr.573 = "3, 13, or 23")
• When the analog current input becomes 2 mA or lower, 4 mA input fault (E.LCI) will be activated after the deceleration stop
and the output is shut off.
• When the analog current input is restored during the deceleration, it will accelerate again and operate according to the
current input.
• The following is the operation example during PID control (reverse action) operation.
Output frequency
20 mA
Set point (fixed)
Measured value
4 mA
STF
LF signal
PID signal
ALM signal
• The following is the operation example when the analog input current is restored during deceleration under PID control
(reverse action).
Output frequency
20 mA
Set point (fixed)
Measured value
4 mA
STF
LF signal
PID signal
Decelerates as the input current is lost
After deceleration stop, E.LCI occurs
Input current
decrease
Return
3 mA
2 mA
Decelerates as the input current is lost
Normal operation after the current is restored
Input current
decrease
Return
3 mA
2 mA
OFF during
deceleration
Time
Time