5.11.10 Multi-pump function (Advanced PID function)
PID control function can adjust the volume of water, etc. by controlling pumps. When the motor output is insufficient, auxiliary
motors can be driven by the commercial power supply. Up to three auxiliary motors can be connected.
Pr.
Name
578
Auxiliary motor operation
A400
selection
579
Motor connection function
A401
selection
580
MC switchcover interlock
A402
time (multi-pump)
581
Start waiting time (multi-
A403
pump)
582
Auxiliary motor connection-
A404
time deceleration time
583
Auxiliary motor
A405
disconnection-time
acceleration time
584
Auxiliary motor 1 starting
A406
frequency
585
Auxiliary motor 2 starting
A407
frequency
586
Auxiliary motor 3 starting
A408
frequency
587
Auxiliary motor 1 stopping
A409
frequency
588
Auxiliary motor 2 stopping
A410
frequency
589
Auxiliary motor 3 stopping
A411
frequency
590
Auxiliary motor start
A412
detection time
591
Auxiliary motor stop
A413
detection time
1370
Detection time for PID
A442
limiting operation
1376
Auxiliary motor stopping
A414
level
• Refer to
page 396
• When using the sleep function, refer to
Initial value
Setting
range
0
0
1 to 3
0
0
1
2
3
1 s
0 to 100 s
1 s
0 to 100 s
1 s
0 to 3600 s
9999
1 s
0 to 3600 s
9999
60 Hz
0 to 590 Hz
60 Hz
0 to 590 Hz
60 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
5 s
0 to 3600 s
5 s
0 to 3600 s
0 s
0 to 900 s
9999
0 to 100%
9999
to set PID control.
page 408
Description
No auxiliary motor operation
Set the number of auxiliary motors to be run.
Basic system
Alternative system
Direct system
Alternative direct system
Set the MC switchover interlock time.
Set the time from when the MC is switched until it starts. Set
this time a little longer than the MC switching time.
Used to decrease the output frequency of the inverter when a
motor connection occurs. Set the deceleration time for
decreasing the output frequency.
The output frequency is not decreased when a motor
connection occurs.
Used to increase the output frequency of the inverter when a
motor connection occurs. Set the acceleration time for
increasing the output frequency.
The output frequency is not increased when a motor
connection occurs.
Set the frequency to start the auxiliary motor.
Set the frequency to stop the auxiliary motor.
Set the delay time until the auxiliary motor is started.
Set the delay time until the auxiliary motor is stopped.
Set the time until the auxiliary motor is stopped when the PID
overpressure control function is used.
Set the level for stopping the auxiliary motor by the PID
overpressure control function.
The PID overpressure control function is disabled.
to set the function.
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10
429
5. PARAMETERS