NOTE
• When using separate power supplies, always remove the jumpers across terminals R/L1 and R1/L11 and across S/L2 and
S1/L21. The inverter may be damaged if the jumpers are not removed.
• The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other
than the input side of the MC.
• The power capacity necessary when separate power is supplied from R1/L11 and S1/L21 differs according to the inverter
capacity.
Inverter
FR-F860-00170 or lower
FR-F860-00320 or higher
• If the main circuit power is switched OFF (for 0.1 s or more) then ON again, the inverter is reset and a fault output will not
be held.
• When a power supply is provided for the control circuit separately from the main circuit and a capacitive device (such as
an EMC filter or a radio noise filter) is connected, refer to the following diagram.
62
2. INSTALLATION AND WIRING
2.6 Control circuit
Power supply capacity
60 VA
80 VA
MC
Capacitive
device
R/L1
S/L2
T/L3
R1/L11
S1/L21