5.4.14
Parameter copy alarm release
The parameter copy alarm can be canceled. The parameter copy alarm is generated when parameter copy is performed
between the FR-F860-00680 or lower and the FR-F860-01080 or higher.
Pr.
Name
989
Parameter copy alarm release
E490
*1
The setting range or initial value for the FR-F860-00680 or lower.
*2
The setting range or initial value for the FR-F860-01080 or higher.
• The setting range of some parameters differ between the FR-F860-00680 or lower and the FR-F860-01080 or higher.
When parameter copy is performed between the FR-F860-00680 or lower and the FR-F860-01080 or higher, the
parameter copy alarm (CP) is displayed on the operation panel because resetting of some parameters is necessary.
• Use Pr.989 to cancel the parameter copy alarm. After setting Pr.989, perform setting of Pr.9, Pr.30, Pr.51, Pr.56, Pr.57,
Pr.61, Pr.70, Pr.72, Pr.80, Pr.82, Pr.90 to Pr.94, Pr.453, Pr.455, Pr.458 to Pr.462, Pr.557, Pr.859, Pr.860, and Pr.893
again.
5.4.15
PWM carrier frequency and Soft-PWM control
The motor sound can be changed.
Pr.
Name
72
PWM frequency selection
E600
240
Soft-PWM operation selection
E601
260
PWM frequency automatic
E602
switchover
*1
The setting range for the FR-F860-00680 or lower.
*2
The setting range for the FR-F860-01080 or higher.
 Changing the PWM carrier frequency (Pr.72)
• The PWM carrier frequency of the inverter can be changed.
• Changing the PWM carrier frequency can be effective for avoiding the resonance frequency of the mechanical system or
motor, as a countermeasure against EMI generated from the inverter, or for reducing leakage current caused by PWM
switching.
Initial value
Setting range
*1
*1
10
10
*2
100
*2
100
Initial value
Setting range
2
*1
0 to 15
*2
0 to 6, 25
1
0
1
1
0
1
Description
Cancels the alarm of FR-F860-00680 or lower.
Cancels the alarm of FR-F860-01080 or higher.
Description
The PWM carrier frequency can be changed. The
setting displayed is in [kHz]. Note that 0 indicates 0.7
kHz, and 15 indicates 14.5 kHz. (The setting value
"25" is for manufacturer setting. Do not set.)
Soft-PWM disabled
The soft-PWM is enabled.
PWM carrier frequency automatic reduction function
disabled (for the LD rating)
PWM carrier frequency automatic reduction function
enabled
5.4 (E) Environment setting parameters
3
4
5
5
5
6
7
8
9
10
179
5. PARAMETERS