 Trigger setting (Pr.1025, Pr.1035 to Pr.1037, Pr.1046, Pr.1047)
• Set the trigger generating conditions and trigger target channels.
Pr.1025 setting
0
Trace starts when inverter enters an fault status (protective function activated)
1
Trace starts when analog monitor satisfies trigger conditions
2
Trace starts when digital monitor satisfies trigger conditions
3
Trace starts when either of analog or digital monitor satisfies trigger conditions (OR)
4
Trace starts when both of analog or digital monitor satisfies trigger conditions (AND)
• Set the trigger generation conditions for the analog monitor.
Pr.1036 setting
0
Sampling starts when the analog data targeted for the trigger exceeds the value specified
at the trigger level
1
Sampling starts when the analog data targeted for the trigger has fallen below the value
specified at the trigger level
*1
For Pr.1037, set the number obtained by adding 1,000 to the trigger level.
• Set the trigger generation conditions for the digital monitor.
Pr.1047 setting
0
Trace starts when the digital data targeted for the trigger turns ON
1
Trace starts when the digital data targeted for the trigger turns OFF
 Start of sampling and copying of data (Pr.1020, Pr.1024)
• Set the trace operation. The trace operation is set by setting Pr.1020 Trace operation selection.
• When "1" is set in Pr.1020, sampling is started.
• When "2" is set in Pr.1020, a trigger is regarded as having been generated (for instance, a forced trigger), sampling is
stopped and the trace is started.
• When "3" is set in Pr.1020, sampling is stopped.
• When "4" is set in Pr.1020, the trace data in internal RAM is transferred to a USB memory device. (Trace data cannot be
transferred during sampling.)
• To automatically start sampling when the power supply is turned ON or at a recovery after an inverter reset, set "1" to
Pr.1024 Sampling auto start.
Pr.1020 setting
0
Sampling standby
1
Sampling start
2
Forced trigger (sampling stop)
3
Sampling stop
4
Data transmission
• The read value of Pr.1020 is always "0".
 Selection of trace operation by input terminal (TRG signal, TRC signal)
• Trace operation can be selected by signal inputs.
• A forced trigger can be applied when the Trace trigger input (TRG) signal is ON.
• Sampling is started and stopped by the Trace sampling start/end (TRC) signal turning ON and OFF, respectively.
• To input the TRG signal, set "46" in any of Pr.178 to Pr.189 (Input terminal function selection), and to input the TRC
signal, set "47" to assign the function to a terminal.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Trigger generating conditions
Trigger generation conditions
Trigger generation conditions
Operation
Selection of trigger target
channel
Pr.1035
Pr.1046
Pr.1035, Pr.1046
Pr.1035, Pr.1046
Trigger level setting
Set the trigger level by
*1
Pr.1037 (-400% to 400%)
5. PARAMETERS
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10