5.8.3
Monitor display selection for terminals CA and AM
The monitored status can be output as the following items: analog voltage (terminal AM), analog current (terminal CA).
The signal (monitored item) to be output to terminal CA and terminal AM can be selected.
Pr.
54
CA terminal function selection
M300
158
AM terminal function selection
M301
55
Frequency monitoring reference
M040
56
Current monitoring reference
M041
866
Torque monitoring reference
M042
290
Monitor negative output
M044
selection
291
Pulse train I/O selection
D100
*1
FR-F860-00680 or lower.
*2
FR-F860-01080 or higher.
*3
Function assigned to Pr.185 JOG terminal function selection.
 Monitor description list (Pr.54, Pr.158)
• Set Pr.54 CA terminal function selection for the monitor to be output to the terminal CA (analog current output).
• Set Pr.158 AM terminal function selection for the monitor to be output to the terminal AM (analog voltage output). Output
with a negative sign can be made (-10 VDC to +10 VDC) from the terminal AM.  in the [Negative (-) output] indicates the
output value is negative at the terminal AM. (For setting of the output with/without minus sign, refer to
• Refer to the following table and set the monitor to be displayed. (Refer to
Monitor item
Output frequency
*2
Output current
Output voltage
Frequency setting value
Running speed
Motor torque
Converter output voltage
Electronic thermal O/L
relay load factor
Output current peak value
Converter output voltage
peak value
Input power
284
5. PARAMETERS
5.8 (M) Monitor display and monitor output signal
Name
Initial value
1
(output
frequency)
60 Hz
Inverter rated
current
150%
0
0
Increment and
Pr.54 (CA)
unit
Pr.158 (AM)
setting
0.01 Hz
1
*1
2
0.01 A/0.1 A
0.1 V
3
0.01 Hz
5
1 (r/min)
6
0.1%
7
0.1 V
8
*2
9
0.1%
10
*1
11
0.01 A/0.1 A
0.1 V
12
0.01 kW/0.1
13
*1
kW
Setting range
1 to 3, 5 to 14, 17, 18,
Select the monitored item to be output to the
21, 24, 34, 50, 52, 53,
terminal CA.
61, 62, 67, 69, 70, 85,
87 to 90, 92, 93, 95, 98
1 to 3, 5 to 14, 17, 18,
Select the monitored item to be output to the
21, 24, 34, 50, 52 to 54,
terminal AM.
61, 62, 67, 69, 70, 86 to
96, 98
0 to 590 Hz
Set the full-scale value when outputting the
frequency monitor value to terminals CA and
AM.
*1
Set the full-scale value when outputting the
0 to 500 A
output current monitor value to terminals CA
*2
0 to 3600 A
and AM.
0 to 400%
Set the full-scale value when outputting the
torque monitor value to terminals CA and AM.
0 to 7
Set the availability of output with a minus sign
for the terminal AM, the operation panel
display, or monitoring via communication.
(Refer to
0
The JOG signal is assigned to terminal
JOG.
1
Pulse train input is assigned to terminal JOG.
page 275
Terminal CA/AM
Negative
full-scale value
(-) output
Pr.55
*3
Pr.56
1000 V
Pr.55
Value is Pr.55 converted
*3
by Pr.37, Pr.144. (Refer
to
page
272.)
Pr.866
1000 V
Electronic thermal O/L
relay operation level
(100%)
Pr.56
1000 V
Inverter rated power  2
Description
page
282)
*3
page
274.)
for the monitor description.)
Remarks
Refer to
page 272
for the
running speed monitor.
For manufacturer setting. Do
not set.