Mitsubishi Electric 800 Series Instruction Manual page 523

Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Supported BACnet object
 ANALOG INPUT
Object
identifier
0
Terminal 1
1
Terminal 2
2
Terminal 4
*1
R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
 ANALOG OUTPUT
Object
identifier
0
Terminal CA
1
Terminal AM
*1
R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array, even when "Write Access Denied" is returned
due to inconsistency of the writing requirements such as the operating mode, on condition that the values are written within the setting range.
*2
Available regardless of the operation mode, operation command source, and speed command source.
 ANALOG VALUE
Object
identifier
1
Output frequency
2
Output current
3
Output voltage
6
Running speed
8
Converter output
voltage
14
Output power
17
Load meter
20
Cumulative
energization time
23
Actual operation time
522
5. PARAMETERS
5.12 (N) Operation via communication and its settings
Object name
Present value
access type
R
R
R
Object name
Present value
access type
C
C
Object name
Present value
access type
R
R
R
R
R
R
R
R
R
Description
*1
Represents actual input voltage of terminal 1.
(The range varies depending on the Pr.73 and Pr.267
settings.
-10 to +10 V (-100% to +100%),
-5 to +5 V (-100% to +100%))
Represents actual input voltage (or input current) of terminal
2.
(The range varies depending on the Pr.73 and Pr.267
settings.
0 to 10 V (0% to 100%),
0 to 5 V (0% to 100%),
0 to 20 mA (0% to 100%))
Represents actual input voltage (or input current) of terminal
4.
(The range varies depending on the Pr.73 and Pr.267
settings.
2 to 10 V (0% to 100%),
1 to 5 V (0% to 100%),
4 to 20 mA (0% to 100%))
Description
*1
Controls actual output current level of terminal CA.
Control is available when Pr.54 CA terminal function
*2
selection="85"
.
(Setting range: 0 to 200%)
Controls actual output voltage level of terminal AM.
Control is available when Pr.158 AM terminal function
*2
selection="86"
.
(Setting range: -200 to 200%)
Description
*1
Represents the output frequency monitor.
Represents the output current monitor.
Represents the output voltage monitor.
Represents the running speed monitor.
Represents the converter output voltage monitor.
Represents the output power monitor.
Represents the load meter monitor.
Represents the cumulative energization time monitor.
Represents the actual operation time monitor.
Unit
percent
(98)
percent
(98)
percent
(98)
Unit
percent
(98)
percent
(98)
Unit
hertz
(27)
amperes
(3)
volts
(5)
revolution-
per-minute
(104)
volts
(5)
kilowatts
(48)
percent
(98)
hours
(71)
hours
(71)