Pr.128
Pr.609
PID action
setting
Pr.610
1000
Valid
Reverse action
1001
Forward action
1010
Reverse action
1011
Forward action
2000
Reverse action (without
frequency reflected)
2001
Forward action (without
frequency reflected)
2010
Reverse action (without
frequency reflected)
2011
Forward action (without
frequency reflected)
When Pr.133  "9999", the Pr.133 setting is valid.
*1
*2
BACnet MS/TP, CC-Link, CC-Link IE Field Network, or LONWORKS communication is available. For details on BACnet MS/TP protocol, refer to
page
516. For details of other types of communication, refer to the Instruction Manual of each option.
*3
For details on the PLC function, refer to the PLC Function Programming Manual.
• The set point/deviation input method can also be flexibly selected by Pr.609 PID set point/deviation input selection and
the measured value input method can be selected by Pr.610 PID measured value input selection. Selection by Pr.609
and Pr.610 is valid when Pr.128 = "1000 to 2011".
Setting value
Pr.609
Pr.610
1
1
Terminal 1
2
2
Terminal 2
3
3
Terminal 4
4
4
Communication
5
5
PLC function
101
Terminal 1
102
Terminal 2
103
Terminal 4
104
Communication
105
PLC function
*4
When the same command source has been selected for the set point and measured value using Pr.609 and Pr.610, set point input is invalid.
(The inverter runs at set point 0%)
*5
BACnet MS/TP, CC-Link, CC-Link IE Field Network, or LONWORKS communication is available. For details on BACnet MS/TP protocol, refer to
page
516. For details of other types of communication, refer to the Instruction Manual of each option.
• When Pr.610 PID measured value input selection = "101 to 105", the square root of the input value is used as the
measured value.
NOTE
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using Pr.902 and Pr.904 to prevent a
minus voltage from being entered as the deviation input signal. Input of a minus voltage might damage devices and the
inverter.
Set point input
According to Pr.609
According to Pr.609
Command source
Input method
Direct input
*4
*4
*4
*5
*4
Square root input
*4
*4
*5
Flow rate ∝
Pressure
Measured value input
According to Pr.610
*1
*1
According to Pr.610
Pressure (measured value)
Pressure
(measured value
used for controlling)
Flow rate
Deviation input
According to Pr.609
According to Pr.609
5. PARAMETERS
5.11 (A) Application parameters
3
4
5
5
5
6
7
8
9
10